M13765-1 v5
Table 90. Indications
Function Value
Buffer capacity Maximum number of indications presented for single disturbance 352
Maximum number of recorded disturbances 100
M12702-1 v4
Table 91. Event recorder
Function Value
Buffer capacity Maximum number of events in disturbance report 150
Maximum number of disturbance reports 100
Resolution 1 ms
Accuracy Depending on time
synchronizing
M13747-1 v5
Table 92. Trip value recorder
Function Value
Buffer capacity
Maximum number of analog inputs 30
Maximum number of disturbance reports 100
M12384-1 v7
Table 93. Disturbance recorder
Function Value
Buffer capacity Maximum number of analog inputs 40
Maximum number of binary inputs 352
Maximum number of disturbance reports 100
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
340 seconds (100 recordings) at 50 Hz
280 seconds (80 recordings) at 60 Hz
GUID-C43B8654-60FE-4E20-8328-754C238F4AD0 v3
Table 94. Event counter with limit supervision L4UFCNT
Function Range or value Accuracy
Counter value 0-65535 -
Max. count up speed 30 pulses/s (50% duty cycle) -
GUID-F5E124E3-0B85-41AC-9830-A2362FD289F2 v1
Table 95. Running hour-meter TEILGAPC
Function Range or value Accuracy
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value
Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%
1MRK 506 384-BEN A
Line distance protection REL650 2.2
Product version: 2.2.1
68 ABB