GUID-0FB9BAD2-E624-4310-A267-6E71E936A803 V1 EN
Figure 78: ISWGAPC3
ISWGAPC4
ISWGAPC4 input is used to configure which protection function is blocked by the
autoreclosing function by changing the ISWGAPC4 parameters. ISWGAPC4 input is
routed from DARREC1 output PROT_CRD. ISWGAPC4 outputs are connected to the
BLOCK inputs of some of the protection functions.
GUID-C935C34F-80CD-4A23-99BC-D997FC45B22F V1 EN
Figure 79: ISWGAPC4
SELGAPC2
SELGAPC2 inputs are the circuit breaker closed and open positions routed from
SELGACP1. SELGAPC2 outputs are routed to the BLOCK input of the trip circuit
supervision functions TCSSCBR1 and TCSSCBR2.
By default, X100-PO3 and PO4 are both used for the open circuit breaker.
TCSSCBR1 and TCSSCBR2 are both blocked by the circuit breaker open position. If
X100-PO3 is used for closing the circuit breaker, TCSSCBR1 need to be blocked by
the circuit breaker close position (OUT_1 connection=IN_1). If X100-PO4 is used for