Table 35. Directional earth-fault protection (DEFxPDEF) main settings
Parameter Function Value (Range) Step
Start Value DEFLPDEF 0.010...5.000 pu 0.005
DEFHPDEF 0.10...40.00 pu 0.01
Directional mode DEFLPDEF and
DEFHPDEF
1=Non-directional
2=Forward
3=Reverse
Time multiplier DEFLPDEF 0.05...15.00 0.05
DEFHPDEF 0.05...15.00 0.05
Operate delay time DEFLPDEF 0.06...200.00 s 0.01
DEFHPDEF 0.06...200.00 s 0.01
Operating curve
type
1)
DEFLPDEF Definite or inverse time
Curve type: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,
13, 14, 15, 17, 18, 19
DEFHPDEF Definite or inverse time
Curve type: 1, 3, 5, 15, 17
Operation mode DEFLPDEF and
DEFHPDEF
1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
1) For further reference, refer to the Operating characteristics table
Table 36. Rotor earth-fault protection (MREFPTOC)
Characteristic
Value
Operation accuracy Depending on the frequency of the current
measured f=fn ± 2 Hz
±1.5% of the set value or ±0.002 x In
Start time
1)2)
Typical 25 ms (+-15ms)
Reset time < 50 ms
Reset ratio Typical 0.96
Retardation time < 50 ms
Operate time accuracy ±1.0% of the set value of ±20 ms
Suppression of harmonics -50dB at f = n x fn, where n = 2, 3, 4, 5,…
1) Current before fault = 0.0 x In, fn = 50 Hz, earth-fault current with nominal frequency injected from random
phase angle, results based on statistical distribution of 1000 measurements.
2) Includes the delay of the signal output contact.