Table 60. Positive-sequence overvoltage protection (PSPTOV)
Characteristic Value
Operation accuracy At the frequency f = f
n
±1.5% of the set value or ±0.002 x U
n
Start time
1)2)
U
Fault
= 1.1 x set
Start value
U
Fault
= 2.0 x set
Start value
Typical: 29 ms (±15 ms)
Typical: 24 ms (±15 ms)
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,
…
1) Positive-sequence voltage before fault = 0.0 x U
n
, f
n
= 50 Hz, positive-sequence overvoltage of nominal frequency
injected from random phase angle
2) Includes the delay of the signal output contact
Table 61. Positive-sequence overvoltage protection (PSPTOV) main settings
Parameter
Function Value (Range) Step
Start value PSPTOV 0.800...1.600 pu 0.001
Operate delay time PSPTOV 0.040...120.000 s 0.001
Motor Protection and Control 1MRS756977 D
REM630
Product version: 1.1 Issued: 2011-05-18
42 ABB