Table 36. Breaker failure protection CCRBRF
Function Range or value Accuracy
Operate phase current (5-200)% of
lBase
± 1.0% of I
r
at I £ I
r
± 1.0% of I at I > I
r
Reset ratio, phase current > 95% -
Operate residual current (2-200)% of
lBase
± 1.0% of I
r
at I £ I
r
± 1.0% of I at I > I
r
Reset ratio, residual current > 95% -
Phase current level for blocking of contact function (5-200)% of
lBase
± 1.0% of I
r
at I £ I
r
± 1.0% of I at I > I
r
Reset ratio > 95% -
Timers (0.000-60.000) s ± 0.5% ±10 ms
Operate time for current detection 10 ms typically -
Reset time for current detection 15 ms maximum -
Table 37. Pole discordance protection CCRPLD
Function Range or value Accuracy
Operate current (0–100)% of
IBase
± 1.0% of I
r
Time delay (0.000-60.000) s ± 0.5% ± 10 ms
Table 38. Directional underpower protection GUPPDUP
Function
Range or value Accuracy
Power level (0.0–500.0)% of
SBase
At low setting:
(0.5-2.0)% of
SBase
(2.0-10)% of
SBase
± 1.0% of S
r
at S < S
r
± 1.0% of S at S > S
r
< ± 50% of set value
< ± 20% of set value
Characteristic angle (-180.0–180.0) degrees 2 degrees
Timers (0.00-6000.00) s ± 0.5% ± 10 ms
Table 39. Directional overpower protection GOPPDOP
Function
Range or value Accuracy
Power level (0.0–500.0)% of S
base
At low setting:
(0.5-2.0)% of S
base
(2.0-10)% of S
base
± 1.0% of S
r
at S < S
r
± 1.0% of S at S > S
r
< ± 50% of set value
< ± 20% of set value
Characteristic angle (-180.0–180.0) degrees 2 degrees
Timers (0.00-6000.00) s ± 0.5% ± 10 ms
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
44 ABB