EasyManua.ls Logo

ABB SPAM 150 C - Page 11

ABB SPAM 150 C
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11
Motor protection relay module SPCJ 4D34
Thermal overload unit
Setting of full load current, I
θ
0.5...1.50 x I
n
Resolution of current setting 0.01 x I
n
Setting of maximum stall time, t
6x
2.0...120 s
Resolution of stall time-setting 0.5 s
Cooling time-constant k
c
at zero current (standstill) 1...64 x the heating time constant
Thermal prior alarm level θ
a
, if in use 50...100% of the thermal trip level θ
t
Restart inhibit level θ
i
20...80% of the thermal trip level θ
t
Thermal unit initialization after an auxiliary
supply interrupt *) 70% of the thermal trip level θ
t
,
i.e. hot motor
Low-set overcurrent unit **)
Setting range for I> 1.0...10.0 x I
n
Operate time t> 0.3…80 s
Current based start-up supervision **)
Startup current setting range I
s
1.0...10.0 x I
n
Startup time setting range t
s
0.3…80 s
Shortest operate time ~300 ms
High-set overcurrent unit
Setting range for I>> 0.5...20.0 x I
n
and , infinite
Operate time t>> 0.04...30 s
Earth-fault protection unit
Setting range for I
0
1.0...100% I
n
Operate time t
0
0.05...30 s
Attenuation of the third harmonic, typ. -20 dB
Phase unbalance unit
Basic sensitivity I, stabilized to phase current
levels below I
θ
10...40% x I
L
and , infinite
Operate time at lowest settable pick-up level, 10 % 20...120 s, inverse time
Operate time at full unbalance (single phasing) 1 s
Operate time incorrect phase sequence protection 600 ms
Undercurrent unit
Start current I< in per cent of the full load
current setting 30...80% I
θ
or out of operation
Operation inhibited below level 12% I
θ
Operate time 2...600 s
Time-based start inhibit counter
Setting range t
si
5...500 s
Countdown rate of start time counter t
s
/t 2...250 s / h
Note!
*) If the thermal prior alarm is set below 70%, the connection of the auxiliary supply to the relay
will cause a thermal prior alarm signal.
**)The operation can be defined either as a low-set definite time overcurrent function (SGF/7 = 0)
or as a current based start-up supervision function (SGF/7=1). Both functions cannot be used
at the same time. In either case, the time-counting can be stopped by a control signal to the speed
switch input (SGB/1 =1).

Other manuals for ABB SPAM 150 C

Related product manuals