8
Settings
The setting values are indicated by the three
rightmost digits of the display. The LED indi-
cators adjacent to the setting value symbols in-
dicate the setting value being presented on the
display. Additional setting values are indicated
by the leftmost red digit of the display. The set-
tings can be entered from the push-buttons on
the front panel or over the serial port.
Symbol Description Setting range Default
U
s
Reference voltage (set voltage) 0.85...1.15 x U
n
1.00 x U
n
∆U
s
Bandwidth 0.60...9.00% x U
n
1.50%
T1 Delay time for the first control pulse 0.0...300 s 60.0 s
T2 Delay time for the following control pulse, unless 0.0...300 s 30.0 s
U
m
is within the ∆Us limits after the first pulse
I> Overcurrent blocking. Blocks any control 1.00...2.00 x I
n
2.00
operation during an overcurrent situation
U< Undervoltage blocking. Blocks automatic control 0.70... 0.95 x U
n
0.70
during an undervoltage situation
U> Overvoltage detection. If the measured voltage 1.05...1.25 x U
n
1.25
exceeds the setting value, lower pulses are given
faster than normally
U
r
[%] Resistive line-drop compensating factor 0.0...25.0% x U
n
0.0
U
x
[%] Reactive line-drop compensating factor 0.0...25.0% x U
n
0.0
1 Checksum of switchgroup SGF1 0...255 16
2 Checksum of switchgroup SGF2 0...255 28
3 Operation counter. Shows the number of raise 0
and lower operations.
Note! The control pulses given manually by using
push-buttons are not counted.
4 Reduce set voltage (RSV). 0
Setting range 0.00...9.00% x U
n
5 Rated current Int of the power transformer. 0.10
To be set, when the module is used in parallel
operation. Setting range 0.10...5.00 kA
6I
nt
/I
ct
ratio, i.e. the ratio between the rated current 1
of the power transformer and the rated primary
current of the current transformer.
Setting range 0.60...1.50
7 Stability factor. Setting range 0...70% x Un 0
8 Output pulse duration (OPD) 1.5
Setting range 0.5...10.0 s
9 Load phase-shift, only used with the negative 0...±60° 0°
reactance principle +° inductive load
Note! For negative setting values: The sign (-) can -° capacitive load
be set only from the leftmost green digit.