EasyManuals Logo

ABB VM1 Manual

ABB VM1
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
14
VM1 - INSTRUCTION MANUAL BA 504/05 E
6.5 Circuit breaker operation
(Figures 9/17 to 9/21)
The power supply has been established when the
“READY“ lamp 2 lights up.
Please also note the remarks in Section 3.1.5.
1. Closing:
• Remote control by applying a voltage to input
-MC (see sections 10.1.1a and 6.2) or locally by
pressing ON pushbutton 3.
2. Opening:
• Remote control by applying a voltage to input
-M01 (see also sections 10.1.1a and 6.2) or
locally by pressing OFF push-button 4.
3. Opening in case of power failure:
a) Opening via the remote control system or by
pressing push-button 4 is initially still
possible:
- up to 60 seconds for breaking currents up
to 25 kA
- up to 120 seconds for breaking currents up
to 31.5 kA.
b) Manual emergency opening is possible
beyond these times.
Insert emergency manual operation lever 28
into socket 8 in the front plate and turn it
anti-clockwise to open the circuit breaker.
During this the auxiliary spring 29 on the
lever 28 will be charged at first. After a
movement of about 65° to 70° a resistance
must be overcome which is generated from
the removal of the armature in the actuator.
Then the circuit breaker is swiched off. A
further rotation will be a free movement.
c) On power failure and after expiry of the
times stated under 3a), the circuit breaker
remains in its current position. If an
automatic switch-off is desired
immediately on expiry of the times stated
under 3a), this behaviour can be effected
by cactivating DIP switch I 1004/1 (see
figure 9/16a, “AUTO-OFF on declining
capacitor voltage”).
4. Closing on failure of the supply voltage:
Closing is not appropriate and not possible.
5. Operating cycle and position indicators on
the switching device:
After each operating cycle (ON-OFF), the
operating cycle counter 5 is incremented by
one full digit.
On termination of a switching operation, the
position indicator 6 displays the relevant
switch position.
6. Anti-pumping system:
• The circuit breaker controller ensures that
closing of the circuit breaker is blocked when
an opening command is active.
• When closing on a subsequent opening
command, further closing with the still active
closing command is blocked. The closing
command must be issued again for the next
closing operation.
6. Commissioning / Operation

Table of Contents

Other manuals for ABB VM1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB VM1 and is the answer not in the manual?

ABB VM1 Specifications

General IconGeneral
BrandABB
ModelVM1
CategoryCircuit breakers
LanguageEnglish

Related product manuals