44
VM1 - INSTRUCTION MANUAL BA 504/05 E
44 VM1 Vacuum circuit-breaker | Instruction manual 504/05
*)
Rail
**)
Front edge of bar
Figure 10/6: Vacuum circuit-breaker on withdrawable part, type VM1
3)
- Use in UniGear-type ZS1 and Powerbloc
- 12 kV, 2000 / 2500 / 3150
4)
, 4000
5)
A, 50 kA
4)
Table 1:
Panel type p N R
Powerbloc
275 694 688
UniGear-type ZS1
275 691±2 688±2
Panel type
Parameters
12
M W U
UniGear-type ZS1
Powerbloc
2000 A, 50 kA 120 79 694
… 4000
5)
A, 50 kA 149 109 694
Table 2:
1)
Only fitted on withdrawable parts for SACE up to 2500 A
2)
Remove the lifting lugs on both sides before commissioning
3)
See table page 40 and 41 (column Dimensional drawings)
4)
Heat sink only fitted for rated currents from 3150 A upwards
5)
Breakers for 4000 A with fan cooling
BA 504-05 GB_29102012.indd 44 30.10.12 13:45
Panel type Parameters M W U
UniGeartypeZS1
Powerbloc
2000A,50kA
12 0 79 694
…4000
5
)A,50kA
14 9 10 9 694
Panel type M W U
UniGeartypeZS1
Powerbloc
275 694 688
14 9
691 ±2 688±2
Figure 10/6: Vacuum circuit breaker on withdrawable part, type VM1 (
3
)
- Use in UniGear-type ZS1 and Powerbloc
- 12 kV, 2000 / 2500 / 3150 4), 4000 5) A, 50 kA
(
1
) Only fitted on withdrawable parts for SACE up to 2500 A
(
2
) Remove the lifting lugs on both sides before commissioning
(
3
) See table page 40 and 41 (column Dimensional drawings)
(
4
) Heat sink only fitted for rated currents from 3150 A upwards
(
5
) Breakers for 4000 A with fan cooling
—
10. Technical data