12
4.3.3. General characteristics
of withdrawable circuit-breakers (15 kV)
for PowerCube PB1 modules 600 mm wide
Circuit-breaker Vmax/W 15
Use in switchgear/enclosure
PowerCube
Standards
IEC 62271-100
CEI EN62271-100 (file 7642)
C37.54 - C37.09 - C37.04 - C37.55
UL Listed (on request)
Rated voltage Ur [kV] 15
Rated insulation voltage Us [kV] 15
Withstand voltage at 50 Hz Ud (1 min) [kV] 36 (at 60 Hz)
Impulse withstand voltage Up [kV] 95
Rated frequency fr [Hz] 60
Rated normal current (40°C) Ir [A] 1200
Rated breaking capacity
(rated symmetrical short-circuit current)
Isc [kA]
25 (3 cycles)
31.5 (3 cycles)
Rated-short time withstand current (2s) Ik [kA]
25
31.5
Making capacity Ip [kA]
65
82
Operation sequence
[O - 0.3" - CO - 15" - CO]
[O - 0.3" - CO - 3' - CO]
Opening time [ms] 27 ... 32.5
Arc duration [ms] 10 ... 17.5
Total interruption time [ms] <50
Closing time [ms] 45 ... 80
Maximum
overall dimensions
H [mm/in] 665/26.18
W [mm/in] 503/19.80
D [mm/in] 662/26.06
Pole centre I [mm/in] 150/5.91
Weight [kg/lb] 98/215.60
Standardized table of dimensions 1VCD003280
Operating temperature [°C] -30 ... +40
Tropicalization IEC: 60068-2-30, 60721-2-1
Electromagnetic compatibility
IEC 62271-1
Standard fittings for withdrawable circuit-breakers for
PowerCube PB1 modules 600 mm wide
The basic versions of the withdrawable circuit-breakers
are three-pole and fitted with:
EL type manual operating mechanism
Mechanical signaling device for closing springs charged/
discharged
Mechanical signaling device for circuit-breaker open/closed
Closing and opening pushbutton
Operation counter
Set of ten auxiliary circuit-breaker open/closed contacts
Lever for manually charging the closing springs
Isolating contacts
D
H
W
I
I