PROTECTION SETTINGS SETUP FOR EKIP TOUCH TRIP UNITS 23
Step 35. Change the Ground Fault Time Delay / Time t4 setting to the value in the coordination study.

minus iconplus iconthe value in the coordination study
Confirm


Ground Fault / G Protection