PRECAUTIONS
• Remove power before wiring. Never connect or
disconnect wiring with the power applied. Do not
allow live wires to touch the circuit board.
• An isolation transformer is recommended when
powering the device with 24 VAC.
• Do not run the wiring in any conduit with line voltage.
• Failure to wire devices with the correct polarity when
using a shared transformer may result in damage to
any device powered by the shared transformer.
• Do not remove the cover. All user features are
accessible from the outside of the unit.
MEDIA
The MLP2 can be used to monitor the dierential pressure
in any application that uses dry air or inert gas.
MOUNTING INSTRUCTIONS
Using the two #8 x 3/4” self drilling mounting screws
supplied by ACI, mount the unit vertically with the brass
ttings pointing towards the ground. Attach the unit to
the mounting surface using the two mounting openings located on the top and bottom anges. This ensures that any
condensation that may form in the tubing does not have an eect on the pressure sensor. If mounting the unit horizontally,
a slight zero shift may occur and care must be taken to prevent moisture from building up in the sensor. For best results, all
tubing lengths should be limited to a maximum length of 75 feet (23 meters).
MLP2 SERIES
Installation & Operation Instructions
Version 6.0
I0000791
FIGURE 1: DLP DIMENSIONS
FRONT
BOTTOM
FIGURE 2: DIN RAIL MOUNTING
0.09"
(2.381 mm)
0.38"
(9.593 mm)
0.36"
(9.198 mm)
3.50"
(88.90 mm)
1.35"
(34.42 mm)
2.10"
(53.32 mm)
ZERO
DIN RAIL
VIN|GND|OUT
Phone: 1-888-967-5224
Website: workaci.com
Question and Answer IconNeed help?

Do you have a question about the aci Zero and is the answer not in the manual?

Summary

Precautions

Media

Mounting Instructions

Vertical Mounting

Mount unit vertically with brass fittings pointing down, using two #8 x 3/4" screws for optimal condensation management.

Horizontal Mounting & Tubing

Horizontal mounting may cause zero shift. Prevent moisture buildup. Limit tubing to 75 feet for best results.

Wiring Instructions

Wiring Connections

Use shielded 16-22AWG cable. Insert wires into depluggable terminal blocks, tightening screws.

Pressure Connections

Zero Adjustment

Product Specifications

Supply Voltage & Output Signals

Details on supported supply voltages (16-36 VDC, 24VAC) and output signal types (4-20mA, 0-5 VDC, 0-10 VDC).

Operating Parameters

Covers temperature ranges (0-85°C), humidity (10-95% RH), thermal effects, warm-up, and response times.

Pressure & Media Compatibility

Specifies proof/burst pressures for different ranges and compatibility with dry air or inert non-conductive gases.

Physical & Electrical Specifications

Includes DIN rail mounting, wire size (14-24 AWG), terminal torque, tubing size, and enclosure material (Polycarbonate).

Warranty & Directives

Warranty Information

ACI MLP2 sensors are covered by a Five (5) Year Limited Warranty.

W.E.E.E. Directive

Guidance on proper disposal of packaging and product at end-of-life to prevent environmental harm.

aci Zero Specifications