PRECAUTIONS
Remove power before wiring. Never connect or
disconnect wiring with the power applied. Do not
allow live wires to touch the circuit board.
An isolation transformer is recommended when
powering the device with 24 VAC.
Do not run the wiring in any conduit with line voltage.
Failure to wire devices with the correct polarity when
using a shared transformer may result in damage to
any device powered by the shared transformer.
Do not remove the cover. All user features are
accessible from the outside of the unit.
MEDIA
The MLP2 can be used to monitor the dierential pressure
in any application that uses dry air or inert gas.
MOUNTING INSTRUCTIONS
Using the two #8 x 3/4” self drilling mounting screws
supplied by ACI, mount the unit vertically with the brass
ttings pointing towards the ground. Attach the unit to
the mounting surface using the two mounting openings located on the top and bottom anges. This ensures that any
condensation that may form in the tubing does not have an eect on the pressure sensor. If mounting the unit horizontally,
a slight zero shift may occur and care must be taken to prevent moisture from building up in the sensor. For best results, all
tubing lengths should be limited to a maximum length of 75 feet (23 meters).
MLP2 SERIES
Installation & Operation Instructions
Version 6.0
I0000791
FIGURE 1: DLP DIMENSIONS
FRONT
BOTTOM
FIGURE 2: DIN RAIL MOUNTING
0.09"
(2.381 mm)
0.38"
(9.593 mm)
0.36"
(9.198 mm)
3.50"
(88.90 mm)
1.35"
(34.42 mm)
2.10"
(53.32 mm)
ZERO
DIN RAIL
VIN|GND|OUT
Phone: 1-888-967-5224
Website: workaci.com
Question and Answer IconNeed help?

Do you have a question about the aci Zero and is the answer not in the manual?

aci Zero Specifications

General IconGeneral
Brandaci
ModelZero
CategoryMeasuring Instruments
LanguageEnglish

Summary

Precautions

Media

Mounting Instructions

Vertical Mounting

Mount unit vertically with brass fittings pointing down, using two #8 x 3/4" screws for optimal condensation management.

Horizontal Mounting & Tubing

Horizontal mounting may cause zero shift. Prevent moisture buildup. Limit tubing to 75 feet for best results.

Wiring Instructions

Wiring Connections

Use shielded 16-22AWG cable. Insert wires into depluggable terminal blocks, tightening screws.

Pressure Connections

Zero Adjustment

Product Specifications

Supply Voltage & Output Signals

Details on supported supply voltages (16-36 VDC, 24VAC) and output signal types (4-20mA, 0-5 VDC, 0-10 VDC).

Operating Parameters

Covers temperature ranges (0-85°C), humidity (10-95% RH), thermal effects, warm-up, and response times.

Pressure & Media Compatibility

Specifies proof/burst pressures for different ranges and compatibility with dry air or inert non-conductive gases.

Physical & Electrical Specifications

Includes DIN rail mounting, wire size (14-24 AWG), terminal torque, tubing size, and enclosure material (Polycarbonate).

Warranty & Directives

Warranty Information

ACI MLP2 sensors are covered by a Five (5) Year Limited Warranty.

W.E.E.E. Directive

Guidance on proper disposal of packaging and product at end-of-life to prevent environmental harm.