MODELS:
MAA1018A-MAA1060A, MGA1072A
(Single Stage)
MAA2060A-MAA2072A, MGA2072A
(2-Stage)
Installation & Operation Manual
10 & 11 EER Vertical Wall-Mount Air Conditioners
Manufactured By:
Marvair, An AirX Climate Solutions Brand
P.O. Box 400 • Cordele, Georgia 31010 • 156 Seedling Drive • Cordele, Georgia 31015
(229) 273-3636 • Fax (229) 273-5154
E-mail: marvairsales@airxcs.com • Internet: www.Marvair.com
The most current version of this manual can be found at www.Marvair.com.
IMPORTANT
This manual may include information for options and features which may not be
included on the unit being installed. Refer to the unit data label or Model Identication
to determine which features and options this unit is equipped with.
INSTALLER: Afx the instructions on the inside of the building adjacent to the thermostat.
END USER: Retain this manual for future reference.
Marvair MAA/MGA Wall Mount AC Installation & Operation Manual
05/2023 Rev.21
Air Conditioner Product Manual
Vertical Wall-Mount Air Conditioners
with Front Control Box Panel

Table of Contents

Questions and Answers

  • M
    Michael McdonaldAug 9, 2025
    What to do if my ACS Marvair MAA1018A blows fuses or trips the circuit breaker?
    • T
      Tina WhiteAug 9, 2025
      If your ACS Air Conditioner is blowing fuses or tripping the circuit breaker, it could be due to several reasons. First, the circuit might not have enough ampacity, so refer to Chapter 2 for electrical requirements and correct as necessary. Second, there might be a short, loose, or improper connection in the field wiring, so check the wiring for errors. Third, there could be an internal short circuit or loose connection within the unit, so check the unit's wiring, referring to the wiring and schematic diagrams, and test components, especially the compressor, for shorts. Finally, excessively high or low supply voltage or phase loss (3ø only) could be the issue, so note the voltage range limitations specific to the compressor troubleshooting section.
  • J
    jason00Aug 15, 2025
    Why does my ACS Air Conditioner run for long periods with insufficient cooling?
    • S
      Steven PattersonAug 15, 2025
      Your ACS Air Conditioner may run for extended periods without sufficient cooling due to several potential issues. A dirty filter or reduced airflow could be the cause, so check the air filter(s), blower operation, and remove any airflow restrictions. Another possibility is low refrigerant, so check for proper charge and possible refrigerant leaks. Component failure, especially of the compressor, could also be responsible, so inspect internal components for proper operation. Finally, the unit might be undersized for the job; in that case, consider adding additional units for greater capacity.
  • A
    alexandersmithAug 20, 2025
    What to do if my ACS Marvair MAA1018A Air Conditioner unit does not run?
    • W
      wilsonbrendaAug 20, 2025
      If your ACS Air Conditioner isn't running, there are several potential causes. First, there might be a power supply problem, so check the power supply for adequate phase and voltage, inspect the wiring to the unit, and check external breakers or fuses. Second, the internal disconnect might have tripped, so check internal circuit protection devices for continuity. Third, an external thermostat may be shut off or defective, so check the operation of the wall-mounted thermostat. Fourth, the unit might be off due to a high or low pressure limit, so reset the pressure switch. Finally, there could be an internal component or connection failure, so check for loose wiring and inspect components for failure.
  • A
    Amy FosterAug 30, 2025
    Why is there water on the floor near my ACS Marvair MAA1018A Air Conditioner?
    • B
      Bryan BradyAug 30, 2025
      If you find water on the floor near your ACS Air Conditioner, it could be due to an obstruction in the condensate line, so check for any clogs or restrictions. Another possibility is an obstruction or leak in the condensate pan, so inspect the pan for leaks or blockages. Lastly, the unit might not be level, so ensure that the unit is properly leveled.
  • B
    bhermanSep 4, 2025
    What to do if my ACS Marvair MAA1018A has no space heating or reduced heating?
    • C
      Christopher MillerSep 4, 2025
      If your ACS Air Conditioner (equipped with resistance elements) has no or reduced space heating, it might be due to defective heating element(s), so check the resistance element(s) for continuity. Another potential cause is an open thermal limit, so check continuity across the thermal limit switch. Lastly, a defective heater contactor could be the issue, so check the relay for proper operation and replace it if defective.
  • D
    Derek RodriguezNov 24, 2025
    What to do if my ACS Air Conditioner cycles on high or low pressure limit?
    • E
      Elizabeth DavisNov 24, 2025
      If your ACS Air Conditioner cycles on a high or low pressure limit, it could be due to several reasons. One possibility is a loss or restriction of airflow, so check the blower assembly for proper operation, look for airflow restrictions such as a dirty air filter, and inspect the blower motor and condenser fan. Another potential cause is a restriction in the refrigerant circuit, so check for blockages or restrictions, especially in the filter drier and capillary tube assembly. Also, refrigerant overcharge (following field service) can cause this issue, so evacuate and recharge the system to factory specifications. Finally, a defective pressure control could be the problem, so check the limit cutout pressures; the control is set to actuate at approximately 60 PSIG (low pressure) and 650 PS...