EasyManua.ls Logo

ACV Delta Performance 25 - Page 13

ACV Delta Performance 25
23 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EN 13
OIL BURNER CHARACTERISTICS
Relay
Burner connector
High viltage transformer
Solenoid valve
Motor
Photoelectric sell
Oil pump
OIL BURNER DESCRIPTION
To fit out our Delta performance Oil boiler we needed a really high
performance burner to give perfect combustion.
We opted to use the brand new technology of the ACV BM R 31,
BM R 51 y BM 101 burners.
Chamber plate (oil)
The chamber plate has 4 screws (M 8 x 20 mm) for the fixing of
the burner. It is protected from the radiation of the flame by an
insulation blanket.
SETTING OIL BURNER PARAMETERS F25 F35 F45 F55
Burner BM R 31 BM R 31 BM R 51 BM 101
Output kW 12 / 48 12 / 48 42 / 60 55 / 130
Electrical power W 150 150 150 185
Nozzle gal/h 0,6 0,75 0,85 1,50
Nozzle angle 60° 60° 60° B 60° B
Oil flow rate kg/h 2,18 2,84 3,60 5,76
Pump pressure bar 11,2 12,0 15,0 10,0
Flue gas index 0,6 0,3 0,4 0,5
Air flap setting 4,5 4,8 4,5 5,0
Combustion head setting 1 2 - 3 4 - 5 4 - 5
Flue pressure drop mbar 0,02 / 0,09 0,08 / 0,09 0,01 / 0,08 0,02 / 0,05
Weight kg 12 12 12 14
Ø112
Ø28
4 x Ø6.5 (M8)
53
53
53 53
BM R 31
BM R 51 BM 101
A mm 240 260
B mm 270 300
C mm 215 250
D mm 280 310
E mm 60 - 130 60 - 150
F M 8 M 8
G mm 80 90
L
Ø
85 95
LK Ø 140 - 165 125 - 180

Other manuals for ACV Delta Performance 25