Identify location for installation of
MagnaClean filter. Prepare pipework
and install filter.
N.B. Refer to MagnaClean installation
instructions.
Turn OFF isolation valves on the
RapidFlush Filter. Loosen and remove
the lid assembly from the RapidFlush
filter canisters.
Removal of black iron oxide and non-
magnetic material and cleanser for open
vented systems.
Identify the three-port valve and
confirm manual operation. If not, install
an isolation valve on the cylinder
flow or return. Complete all relevant
preliminary electrical safety checks to
boiler and pipework confirming safe
isolation and earth path, isolate central
heating system and drain.
1
2
4
Step-by-step
Check jubilee clips are secure
before and during operation.
Having completed the installation
of the MagnaClean filter, remove it
and attach the MagnaCleanse hoses
between the RapidFlush filter and
the MagnaCleanse HTV connector
attached to the isolation valve on the
pipework using the appropriate adaptor.
Ensure drain valve is in the lower hose.
N.B. The flow through MagnaCleanse
RapidFlush filter should enter the
bottom right and exit top left.
3