ADF LINEA 820 NMV ZERO CLEARANCE BOX ASSEMBLY INSTRUCTIONS 1/8/23
3
Dimensions for Build out (Front elevation):
1095mm
1375mm
1065mm
100mm
The hearth beneath the unit must include 6mm cement sheet to 1090mm x
550mm deep. The hearth in front of the unit must include 6mm cement sheet
with minimum 1065mm x 300mm deep.
No combustibles/timber within 300mm from the top of the Zero Clearance box
(i.e., to first noggin), 100mm to each side (stud) and 50mm from the rear. No
combustible material to be used in construction at all in this cavity space.
Fan cable must be below the level of the heater base and exit the cavity below
the level of the heater.