10
Non-Contact, High Voltage Detector 275HVD
The following information provides typical detection distances when using
a lower setting than the line voltage.
Note that the distances may vary with each unit and will be affected based
on the actual environment. The values displayed were conducted in an
ideallabenvironmentandcannotrepresenteacheldenvironment.
SETTING VOLTAGE DISTANCE
240V
AC 500VAC 12" - 32cm
240V
AC 1kVAC 18" - 48cm
240V
AC 2kVAC 29" - 75cm
240V
AC 6kVAC 48" - 124cm
240V
AC 11kVAC 57" - 146cm
240V
AC 22kVAC 89" - 226cm
SETTING VOLTAGE DISTANCE
2kV
AC 6kVAC 16" - 40cm
2kV
AC 11kVAC 20" - 52cm
2kV
AC 22kVAC 24" - 60cm
2kV
AC 33kVAC 36" - 92cm
SETTING VOLTAGE DISTANCE
6kV
AC 11kVAC 24" - 61cm
6kV
AC 22kVAC 29" - 75cm
6kV
AC 33kVAC 41" - 105cm
SETTING VOLTAGE DISTANCE
11kV
AC 22kVAC 13" - 35cm
11kV
AC 33kVAC 16" - 42cm
SETTING VOLTAGE DISTANCE
22kV
AC 33kVAC 14" - 36cm
www.GlobalTestSupply.com