230VAC
- L - N
> 650mm
230VAC
tZE/E' Ž ŶŽƚ ŵŽĚŝĨLJ ƚŚĞƐĞƚƚŝŶŐƐŽĨ ƚŚĞ /ŶǀĞƌƚĞƌĚĞǀŝĐĞ ŶLJŵŽĚŝĨŝĐĂƚŝŽŶƚŽ ƚŚĞ ƉĂƌĂŵĞƚĞƌƐĐŽƵůĚĐĂƵƐĞƚŚĞĚĞǀŝĐĞƚŽ
malfunction. The factory settings are shown on the label attached to the unit.
During cooling operation the indoor
unit removes humidity from the air. The
condensate water must be eliminated
by connecting the appropriate discharge
coupling to the piping of the condensate
discharge system.
In units with "Module 600", the polystyrene
tray has a hole that allows for the complete
draining of the condensate (useful in the
case of disassembly). The drainage hole
must always be closed again with the
rubber plug provided.
The units are fitted as standard with a pump/
float device for raising the condensate from
the tray to the drainage point; it consists of
an electronic card, an electric pump with
non-return valve, and a float with a 3-level
sensor (ON, OFF and Alarm).
The power supply for the floating pump
device must never be interrupted.
In the event of an alarm, the float device
interrupts the flow of water in the coil.
The basin is fitted with an overflow hole to
ensure that the condensate water runs off
if the floating pump device is not working.
In this case dripping can be seen from the
grille.
The pump allows a maximum head of 80cm
from the level of the suspended ceiling; if
this is not high enough you will have to use
an auxiliary device.
You are advised to use rigid piping that is
heat-insulated, to avoid condensation on
the outer surfaces.
SC1 = Condensate discharge (male Ø 16mm)
SC2 = Condensate discharge with siphon (male
TϭϲŵŵͿŶƐƵƌŝŶŐĂǀĞƌƟĐĂůƐĞĐƟŽŶŽĨĂƚůĞĂƐƚϱ
cm (from the pump outlet, upward)
The unit can be connected to a fresh air
suction conduit via the circular flange
accessory applied to the vent. The
application of the flange requires a hole to
be opened up on the side. The connection
with the outside is direct, regardless of
unit ventilation.
The accessory also includes a deflector, to
be assembled inside the unit.
CONNECTIONS FOR THE SUCTION OF FRESH EXTERNAL AIR
The unit can be connected to a conduit
for delivering treated air to an adjacent
room via the circular flange accessory. The
application of the flange requires a hole to
be opened up on the side.
KEEd/KE^&KZd,>/sZzK&dZd/ZdKE:EdZKKD
>dZ/>t/Z/E'^
The unit must be connected directly to an electrical
outlet or to an independent circuit.
The FCLI cassette-type fan coils must be powered
with a current of 230V ~50Hz with an earth con
-
nection;
the line voltage must however remain
within the tolerance of ±10% compared with the
nominal value.
To protect the unit against short circuits, fit an omnip
-
olar thermomagnetic cut out max. 2A 250V (IG)
V on the power line with a minimum opening dis
-
tance between the contacts of 3mm.
tĞƌĞĐŽŵŵĞŶĚƵƐŝŶŐĚŝĨĨĞƌĞŶƚŝĂůĚĞǀŝĐĞƐ
ƐƵŝƚĂďůĞĨŽƌŝŶƚĞƌǀĞŶŝŶŐĨŽƌĐƵƌƌĞŶƚƐŽĨĚŝĨ-
ĨĞƌĞŶƚƚLJƉĞ
sinusoidal AC and pulsating DC
currents suddenly applied or slowly rising.
sinusoidal AC with frequency up to
1000 hz
The electrical power cable must be of the H07 V-K or
N07 V-K type with 450/750V insulation if inside a
tube or raceway. Use cables with double H5vv-F
type insulation for visible cable installation.
When making the connections, follow the wiring
diagrams supplied with the equipment and shown
in this document.
Connect the Inverter to the electric box, using the
cables supplied.
Connect a control panel with thermostat and
ventilation speed control, with
0-10V output. For
the connections, refer to the wiring diagrams of
the fan coil and control panel.
1/50 ~ 1/100
MAX. 800mm
5 cm
MAX. 3000mm
1