TECHNICAL MANUAL
CASSETTE-TYPE FAN COIL
IFCLTY 1112 - 4528511_04
FCL
Replace 1012 - 4528511_03
FCL 32 (600x600)
FCL 36 (600x600)
FCL 42 (600x600)
FCL 62 (600x600)
FCL 72 (600x600)
FCL 34 (600x600)
FCL 38 (600x600)
FCL 44 (600x600)
FCL 64 (600x600)
FCL 82 (840x840)
FCL 102 (840x840)
FCL 122 (840x840)
FCL 84 (840x840)
FCL 104 (840x840)
FCL 124 (840x840)

Other manuals for AERMEC FCL 64

Question and Answer IconNeed help?

Do you have a question about the AERMEC FCL 64 and is the answer not in the manual?

Summary

Declaration of Conformity

Safety Symbols

Electrical and Mechanical Hazards

Symbols indicating electrical hazards and moving parts.

Important Information and Maintenance

Safety and Usage Warnings

General warnings on power, improper use, water temp, cables, and airflow.

Room Environment and Airflow

Guidelines on room ventilation, temperature adjustment, and air jet direction.

Maintenance and Operation

Instructions for filter cleaning, normal operation sounds, and regular checks.

Malfunction Handling

Steps to take in case of unit malfunction, contacting service.

Packaging Details

Description of standard packaging for fan coils.

Unit Description

Unit Purpose

Defines the fan coil as a room air treatment terminal unit.

FCL Version

Description of the FCL as a cassette-type fan coil.

Available Sizes

Lists the two basic sizes: Module 600 and Module 840.

Unit Versions

Describes standard, VL, and V2 versions of the fan coils.

Function Descriptions (GLL-M;R Grilles)

Cooling Operation

Details on setting cooling mode, fan speed, and water valve control.

Heating Operation

Details on setting heating mode, fan speed, and water valve control.

Automatic Operation

How the AUTO mode controls temperature, fan speed, and valve opening.

Heating with Electric Heater

Functions and operation when using an electric heater.

Water Probe Function

Describes the function of the water probe upstream of the valve.

Continuous Ventilation

Operation where ventilation is always active.

Thermostat-Controlled Ventilation

Heating ventilation delayed after thermostat call for pre-heating.

Dehumidification Operation

Requirements and settings for dehumidification mode.

Timer Operation

Setting delay for switching unit on/off.

Full Power Operation

Forcing ventilation to maximum speed.

Voltage Failure Pause

Unit restarts with previous settings after voltage interruption.

Delayed Start-up

Delaying ventilation start-up compared to ignition.

SW4 Probe

Optional probe to measure water temperature.

Emergency Command

AUX key activates 'Auto-Emergency' mode.

Main Components

Unit Description

Overview of the FCL cassette-type fan coil and its applications.

Base Construction

Details on the load-bearing base construction and attached components.

Fastening Brackets

Galvanised steel brackets for unit attachment to the ceiling.

Tray

Description of the polystyrene tray for condensate management.

Thermal Exchange Coil

Details on the copper pipes and aluminium louvres of the coils.

Water Valve

Description of the internal 3-way valve and available versions.

Fan Unit

Details on the axial-centrifugal fan and motor speeds.

Condensate Discharge Device

Description of the condensate drain device with pump and sensors.

Condensate Alarm

Alarm function when condensate level reaches limit.

Water Connections

Description of water connection plates for 2-pipe and 4-pipe systems.

Filtering Section

Details on the air filter in the suction grille.

Suction and Delivery Grille Units (GLL Range)

Details on GLL range grilles as obligatory accessories for FCL units.

GLL 10 M; GLL10 R; GLL20 R Grilles

Description of GLL 10M/10R/20R grilles with electronic thermostat.

GLL 10; GLL20 Grilles

Description of GLL 10/20 grilles for manual control.

Control Panel Accessory

Information on external control panels for GLL units.

Selection Criteria

Operating Limits

Specifies the maximum operating limits for temperature, pressure, and humidity.

Water Temperature Conditions

Conditions for water temperature to prevent air stratification.

Minimum Average Water Temperature

Minimum water temperature to avoid condensate formation.

System Examples

FCL Standard System Examples

Wiring diagrams for standard FCL in 2-pipe and 4-pipe systems.

FCL V2 System Examples

Wiring diagrams for FCL V2 in 2-pipe and 4-pipe systems.

FCL Standard with Electric Heater Examples

Wiring diagrams for standard FCL with electric heater.

FCL V2 with Electric Heater Examples

Wiring diagrams for FCL V2 with electric heater.

FCL VL System Examples

Wiring diagrams for FCL VL without valves.

Technical Data (2-pipe versions)

Heating Capacity and Flow Rates (2-pipe)

Technical data for heating capacity, water flow, and pressure drop.

Cooling Capacity and Flow Rates (2-pipe)

Technical data for cooling capacity, water flow, and pressure drop.

Common Data (Fans, Sound, Power)

Data on fans, sound levels, input power, and protection.

Technical Data (4-pipe versions)

Heating Capacity and Flow Rates (4-pipe)

Technical data for heating capacity, water flow, and pressure drop.

Cooling Capacity and Flow Rates (4-pipe)

Technical data for cooling capacity, water flow, and pressure drop.

Common Data (Fans, Sound, Power) (4-pipe)

Data on fans, sound levels, input power, and protection.

Cooling Capacity - FCL32

Cooling Capacity Correction Factors

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL36

Cooling Capacity Correction Factors (FCL36)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL42

Cooling Capacity Correction Factors (FCL42)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL62

Cooling Capacity Correction Factors (FCL62)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL72

Cooling Capacity Correction Factors (FCL72)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL82

Cooling Capacity Correction Factors (FCL82)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL102

Cooling Capacity Correction Factors (FCL102)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL122

Cooling Capacity Correction Factors (FCL122)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL34

Cooling Capacity Correction Factors (FCL34)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL38

Cooling Capacity Correction Factors (FCL38)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL44

Cooling Capacity Correction Factors (FCL44)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL64

Cooling Capacity Correction Factors (FCL64)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL84

Cooling Capacity Correction Factors (FCL84)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL104

Cooling Capacity Correction Factors (FCL104)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL124

Cooling Capacity Correction Factors (FCL124)

Factors to adjust cooling capacity based on fan speed.

Heating Capacity Curves

Heating Capacity Correction Factors

Factors to adjust heating capacity based on fan speed.

Heating Capacity Curves (Continued)

Heating Capacity Correction Factors (Continued)

Factors to adjust heating capacity based on fan speed.

Main Heating Coil Pressure Drop (VL Version) - Heating

Pressure Drops (Water 50°C)

Pressure drop data for heating coils at 50°C water temperature.

Pressure Drops (Water 70°C)

Pressure drop data for heating coils at 70°C water temperature.

Main Cooling Coil Pressure Drop (VL Version) - Cooling

Pressure Drops (Water 7°C)

Pressure drop data for cooling coils at 7°C water temperature.

Glycol Water Correction Factors

Cooling Function Mode Factors

Correction factors for cooling based on glycol water temperature.

Heating Function Mode Factors

Correction factors for heating based on glycol water temperature.

Glycol Water at 10%

Correction factors for 10% glycol water concentration.

Glycol Water at 20%

Correction factors for 20% glycol water concentration.

Glycol Water at 35%

Correction factors for 35% glycol water concentration.

Sound Power Levels

Sound Pressure Levels

Sound pressure levels expressed in dB(A) for different models and speeds.

Accessories Overview

Obligatory Accessories

Lists essential accessories like grilles and control panels.

Suction and Delivery Grille Units

Details on GLL series suction and delivery grilles.

Standard Control Panels

Electronic and electromechanical control panels for fan coils.

VMF System Grilles with Thermostat

Grilles with integrated VMF System thermostat.

VMF System Wall-Mounted Control Panels

Control panels for managing VMF System networks.

Perimeter Casing Accessory

Housing for aesthetic and protective purposes when installed outside ceiling.

Air Purification Accessory

Accessory for air purification.

Air Delivery; Fresh Air Intake Accessories

Flanges for directing air to adjacent rooms or fresh air intake.

Probe Accessories

Probe accessories for use with standard control panels.

Interface Card Accessories

Interface cards for standard control panels.

Hot Water Circuit Valve Accessories (4-pipe)

Electric Resistor Accessories

VMF System Accessories (GLL_N Grille)

Accessory Details: Grille Units

GLL10; GLL20 Grille Unit

Obligatory intake and delivery grille unit for FCL units.

GLL10 M Grille Unit with Motorised Fins

Obligatory grille unit with motorised fins and remote control.

GLL10 R; GLL20 R Grille Unit

Obligatory intake and delivery grille unit with IR receiver and emergency key.

Accessory Details: VMF System Thermostat Grilles

GLL10 N; GLL20 N Grille Unit with VMF Thermostat

Obligatory grille unit with VMF System thermostat.

Thermostat Control Functions

Functions controlled by the VMF System thermostat.

Accessory Details: Filters and Flanges

FEL10 Electrostatic Filter

Electrostatically pre-charged air filter for GLL grilles.

FCLMC Suction Flange

Galvanised steel housing for outside ceiling installation.

Accessory Details: Flanges for Airflow

KFL Delivery Flange

Delivery flange for directing air to adjacent rooms.

KFL20 Delivery Flange

Delivery flange for directing air to adjacent rooms, up to three per unit.

KFLD Suction Flange

Suction flange for fresh air intake connection.

KFLD20 Suction Flange

Suction flange for fresh air intake, up to two per unit.

Accessory Details: Valve Kits

VHL1; VHL20 3-Way Valves Kit

Motor-driven 3-way valve for heating battery in 4-pipe systems.

VHL2; VHL22 2-Way Valves Kit

Motor-driven 2-way valve for heating battery with variable flow.

Accessory Details: Electric Resistors and Interface Cards

RXLE; RXLE20 Electric Resistor

Electric resistors for heater systems, for FCL units with GLL grilles.

SIT3; SIT5 Interface Cards

Interface cards for connecting fan coils to control panels.

Accessory Details: Temperature Probes

VMF-SW1 Water Temperature Probe (Cold Water)

Probe for VMF System thermostats for cold water circuit in 4-pipe systems.

SW3 Minimum Water Temperature Sensor

Probe for PXAE control panel to detect heating coil water temperature.

SW4 Water Temperature Probe (2-pipe;Hot Water)

Probe for VMF System thermostats for 2-pipe and 4-pipe hot water circuits.

SWA Water and Air Temperature Probe

Probe for FMT20AW panels to detect ambient air or water temperature.

VMF System Control Panels

VMF-E4; VMF-E4 D Wall-Mounted Control Panel

Wall-mounted thermostat control panel for VMF range thermostats.

TTL Network Example (FCLs Only)

Diagram showing a TTL network with only FCL units.

VMF-E5 B;E5 N Network Example (FCLs Only)

Diagram showing a network with VMF supervisor and FCL units.

TTL Network Example (Mixed Fan Coils)

Diagram showing a TTL network with mixed fan coil types.

VMF-E5 B;E5 N Network Example (Mixed Fan Coils)

Diagram showing a VMF network with supervisor and mixed fan coils.

VMF System Supervision

VMF-E5 B;E5 N Supervision Interface

Main supervision interface for VMF-E5B/E5N systems.

Recessed Supervisor Control Panel

Description of VMF-E5B/E5N panels, features, and system management capabilities.

Control Panel Accessories

FMT10 Control Panel

Thermostat for fan coils with simplified controls and 3 speeds.

FMT20 AW Control Panel

Thermostat with LCD display, probe options, and built-in installation.

WMT10 Control Panel

Electromechanical thermostat for 4-pipe, 2-pipe systems with heater.

PX Control Panel

Control panel with selector for manual speed control.

Control Panel Accessories (Continued)

PXAE Control Panel

Multifunction electronic thermostat for fan coils, with simplified controls.

PX2; PX2 C6 Control Panels

Control panels for manual speed control and fan speed selection.

Installation Precautions

System Installation Examples

Wiring diagrams illustrating system configurations.

Maximum Installation Height

Guideline to not install the unit at heights above three metres.

Fresh Air and Adjacent Room Connection

Connecting the unit to fresh air ducts and airflow to adjacent rooms.

Installation of Module 600 Unit

Installation Location Planning

Considerations for choosing the installation location for the machine.

Mounting Rods

Procedure for installing M8 threaded rods for frame support.

Unit Handling with Brackets

Instruction to use brackets for handling, not hydraulic connections.

Electric Box and Grid Accessories

Information on the electric box and its supplied grid accessories.

Safety Cable Attachment

Instruction to fix the safety cable to the electric box and grid frame.

Air Probe Installation (GLL10 M;10 R)

Instructions for installing air probes on GLL10M/10R grilles.

Screw Tightening Torque Warning

Warning on screw tightening torque to avoid damaging the tray.

Unit Levelling

Adjusting unit position using support brackets for level installation.

Functioning Test

Procedure for starting the fan coil and performing a test.

Module 600 Installation Steps

Installation Near a Wall

Guidance for closing flow inlet with gasket when installed near a wall.

Installation of Module 840 Unit

Module 840 Installation Location

Considerations for choosing the installation location for Module 840.

Module 840 Mounting Rods

Procedure for installing M8 threaded rods for Module 840 frame support.

Module 840 Unit Handling

Instruction to use brackets for handling Module 840 units.

Module 840 Electric Box and Grille Accessories

Info on electric box and GLL20/GLL20R grille accessories.

Air Probe Installation (GLL20 R)

Instructions for installing air probes on GLL20R grilles.

Module 840 Screw Torque Warning

Warning on screw tightening torque to avoid damaging the tray.

Module 840 Safety Cable Attachment

Instruction to attach safety cable snap hook to grid frame and fan grid.

Module 840 Unit Levelling

Adjusting Module 840 unit position for level installation.

Module 840 Functioning Test

Procedure for starting Module 840 and performing a test.

Disassembly for Maintenance

Electric Box Maintenance

Procedure for accessing and maintaining the electric box.

Installation Near Wall (Module 600;840)

Connections

Hydraulic Connections

Details on flat stroke fittings, gaskets, and mandatory valve accessory for 4-pipe systems.

Condensate Drain Connections

Instructions for connecting the condensate drain pipe and managing the basin.

External Fresh Air Intake Connections

Connecting the unit to a fresh air intake duct via flange.

Airflow to Adjoining Room Connection

Connecting the unit for conditioned air flow to an adjacent room via flange.

Electric Connections

GLL10; GLL20 Electric Connections

Details on direct connection to outlet or circuit, power supply, and cable requirements.

GLL10 M;10 R;20 R;10 N;20 N Electric Connections

Electric connection details for GLL units with receiver/thermostat.

Filter Installation and Replacement (Module 600)

Filter Installation and Replacement (Module 840)

Dimensional Data [mm] (Module 600 Series)

Dimensional Data [mm] (Module 840 Series)

Wiring Diagrams Legend

FCL GLL10;GLL20 Wiring Diagram

FCL VL GLL10;GLL20 Wiring Diagram

FCL GLL10 M Wiring Diagram

FCL GLL10 R; GLL20 R Wiring Diagram

FCL GLL10;GLL20 Wiring Diagrams with Control Panels

FCL GLL10;GLL20 with WMT10 Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with WMT10 control panel.

FCL GLL10;GLL20 with PXAE Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with PXAE control panel.

FCL GLL10;GLL20 Wiring Diagrams with Control Panels (Continued)

FCL GLL10;GLL20 with FMT10 Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with FMT10 control panel.

FCL GLL10;GLL20 with FMT20 AW Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with FMT20AW control panel.

FCL GLL10 N; GLL20 N Wiring Diagram

FCL VL GLL10 N; GLL20 N Wiring Diagram

System Wiring Examples

FCL System Wiring with PXAE, SIT3, SIT5

Wiring example for FCL units with PXAE and SIT interface cards.

Summary

Declaration of Conformity

Safety Symbols

Electrical and Mechanical Hazards

Symbols indicating electrical hazards and moving parts.

Important Information and Maintenance

Safety and Usage Warnings

General warnings on power, improper use, water temp, cables, and airflow.

Room Environment and Airflow

Guidelines on room ventilation, temperature adjustment, and air jet direction.

Maintenance and Operation

Instructions for filter cleaning, normal operation sounds, and regular checks.

Malfunction Handling

Steps to take in case of unit malfunction, contacting service.

Packaging Details

Description of standard packaging for fan coils.

Unit Description

Unit Purpose

Defines the fan coil as a room air treatment terminal unit.

FCL Version

Description of the FCL as a cassette-type fan coil.

Available Sizes

Lists the two basic sizes: Module 600 and Module 840.

Unit Versions

Describes standard, VL, and V2 versions of the fan coils.

Function Descriptions (GLL-M;R Grilles)

Cooling Operation

Details on setting cooling mode, fan speed, and water valve control.

Heating Operation

Details on setting heating mode, fan speed, and water valve control.

Automatic Operation

How the AUTO mode controls temperature, fan speed, and valve opening.

Heating with Electric Heater

Functions and operation when using an electric heater.

Water Probe Function

Describes the function of the water probe upstream of the valve.

Continuous Ventilation

Operation where ventilation is always active.

Thermostat-Controlled Ventilation

Heating ventilation delayed after thermostat call for pre-heating.

Dehumidification Operation

Requirements and settings for dehumidification mode.

Timer Operation

Setting delay for switching unit on/off.

Full Power Operation

Forcing ventilation to maximum speed.

Voltage Failure Pause

Unit restarts with previous settings after voltage interruption.

Delayed Start-up

Delaying ventilation start-up compared to ignition.

SW4 Probe

Optional probe to measure water temperature.

Emergency Command

AUX key activates 'Auto-Emergency' mode.

Main Components

Unit Description

Overview of the FCL cassette-type fan coil and its applications.

Base Construction

Details on the load-bearing base construction and attached components.

Fastening Brackets

Galvanised steel brackets for unit attachment to the ceiling.

Tray

Description of the polystyrene tray for condensate management.

Thermal Exchange Coil

Details on the copper pipes and aluminium louvres of the coils.

Water Valve

Description of the internal 3-way valve and available versions.

Fan Unit

Details on the axial-centrifugal fan and motor speeds.

Condensate Discharge Device

Description of the condensate drain device with pump and sensors.

Condensate Alarm

Alarm function when condensate level reaches limit.

Water Connections

Description of water connection plates for 2-pipe and 4-pipe systems.

Filtering Section

Details on the air filter in the suction grille.

Suction and Delivery Grille Units (GLL Range)

Details on GLL range grilles as obligatory accessories for FCL units.

GLL 10 M; GLL10 R; GLL20 R Grilles

Description of GLL 10M/10R/20R grilles with electronic thermostat.

GLL 10; GLL20 Grilles

Description of GLL 10/20 grilles for manual control.

Control Panel Accessory

Information on external control panels for GLL units.

Selection Criteria

Operating Limits

Specifies the maximum operating limits for temperature, pressure, and humidity.

Water Temperature Conditions

Conditions for water temperature to prevent air stratification.

Minimum Average Water Temperature

Minimum water temperature to avoid condensate formation.

System Examples

FCL Standard System Examples

Wiring diagrams for standard FCL in 2-pipe and 4-pipe systems.

FCL V2 System Examples

Wiring diagrams for FCL V2 in 2-pipe and 4-pipe systems.

FCL Standard with Electric Heater Examples

Wiring diagrams for standard FCL with electric heater.

FCL V2 with Electric Heater Examples

Wiring diagrams for FCL V2 with electric heater.

FCL VL System Examples

Wiring diagrams for FCL VL without valves.

Technical Data (2-pipe versions)

Heating Capacity and Flow Rates (2-pipe)

Technical data for heating capacity, water flow, and pressure drop.

Cooling Capacity and Flow Rates (2-pipe)

Technical data for cooling capacity, water flow, and pressure drop.

Common Data (Fans, Sound, Power)

Data on fans, sound levels, input power, and protection.

Technical Data (4-pipe versions)

Heating Capacity and Flow Rates (4-pipe)

Technical data for heating capacity, water flow, and pressure drop.

Cooling Capacity and Flow Rates (4-pipe)

Technical data for cooling capacity, water flow, and pressure drop.

Common Data (Fans, Sound, Power) (4-pipe)

Data on fans, sound levels, input power, and protection.

Cooling Capacity - FCL32

Cooling Capacity Correction Factors

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL36

Cooling Capacity Correction Factors (FCL36)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL42

Cooling Capacity Correction Factors (FCL42)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL62

Cooling Capacity Correction Factors (FCL62)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL72

Cooling Capacity Correction Factors (FCL72)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL82

Cooling Capacity Correction Factors (FCL82)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL102

Cooling Capacity Correction Factors (FCL102)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL122

Cooling Capacity Correction Factors (FCL122)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL34

Cooling Capacity Correction Factors (FCL34)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL38

Cooling Capacity Correction Factors (FCL38)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL44

Cooling Capacity Correction Factors (FCL44)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL64

Cooling Capacity Correction Factors (FCL64)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL84

Cooling Capacity Correction Factors (FCL84)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL104

Cooling Capacity Correction Factors (FCL104)

Factors to adjust cooling capacity based on fan speed.

Cooling Capacity - FCL124

Cooling Capacity Correction Factors (FCL124)

Factors to adjust cooling capacity based on fan speed.

Heating Capacity Curves

Heating Capacity Correction Factors

Factors to adjust heating capacity based on fan speed.

Heating Capacity Curves (Continued)

Heating Capacity Correction Factors (Continued)

Factors to adjust heating capacity based on fan speed.

Main Heating Coil Pressure Drop (VL Version) - Heating

Pressure Drops (Water 50°C)

Pressure drop data for heating coils at 50°C water temperature.

Pressure Drops (Water 70°C)

Pressure drop data for heating coils at 70°C water temperature.

Main Cooling Coil Pressure Drop (VL Version) - Cooling

Pressure Drops (Water 7°C)

Pressure drop data for cooling coils at 7°C water temperature.

Glycol Water Correction Factors

Cooling Function Mode Factors

Correction factors for cooling based on glycol water temperature.

Heating Function Mode Factors

Correction factors for heating based on glycol water temperature.

Glycol Water at 10%

Correction factors for 10% glycol water concentration.

Glycol Water at 20%

Correction factors for 20% glycol water concentration.

Glycol Water at 35%

Correction factors for 35% glycol water concentration.

Sound Power Levels

Sound Pressure Levels

Sound pressure levels expressed in dB(A) for different models and speeds.

Accessories Overview

Obligatory Accessories

Lists essential accessories like grilles and control panels.

Suction and Delivery Grille Units

Details on GLL series suction and delivery grilles.

Standard Control Panels

Electronic and electromechanical control panels for fan coils.

VMF System Grilles with Thermostat

Grilles with integrated VMF System thermostat.

VMF System Wall-Mounted Control Panels

Control panels for managing VMF System networks.

Perimeter Casing Accessory

Housing for aesthetic and protective purposes when installed outside ceiling.

Air Purification Accessory

Accessory for air purification.

Air Delivery; Fresh Air Intake Accessories

Flanges for directing air to adjacent rooms or fresh air intake.

Probe Accessories

Probe accessories for use with standard control panels.

Interface Card Accessories

Interface cards for standard control panels.

Hot Water Circuit Valve Accessories (4-pipe)

Electric Resistor Accessories

VMF System Accessories (GLL_N Grille)

Accessory Details: Grille Units

GLL10; GLL20 Grille Unit

Obligatory intake and delivery grille unit for FCL units.

GLL10 M Grille Unit with Motorised Fins

Obligatory grille unit with motorised fins and remote control.

GLL10 R; GLL20 R Grille Unit

Obligatory intake and delivery grille unit with IR receiver and emergency key.

Accessory Details: VMF System Thermostat Grilles

GLL10 N; GLL20 N Grille Unit with VMF Thermostat

Obligatory grille unit with VMF System thermostat.

Thermostat Control Functions

Functions controlled by the VMF System thermostat.

Accessory Details: Filters and Flanges

FEL10 Electrostatic Filter

Electrostatically pre-charged air filter for GLL grilles.

FCLMC Suction Flange

Galvanised steel housing for outside ceiling installation.

Accessory Details: Flanges for Airflow

KFL Delivery Flange

Delivery flange for directing air to adjacent rooms.

KFL20 Delivery Flange

Delivery flange for directing air to adjacent rooms, up to three per unit.

KFLD Suction Flange

Suction flange for fresh air intake connection.

KFLD20 Suction Flange

Suction flange for fresh air intake, up to two per unit.

Accessory Details: Valve Kits

VHL1; VHL20 3-Way Valves Kit

Motor-driven 3-way valve for heating battery in 4-pipe systems.

VHL2; VHL22 2-Way Valves Kit

Motor-driven 2-way valve for heating battery with variable flow.

Accessory Details: Electric Resistors and Interface Cards

RXLE; RXLE20 Electric Resistor

Electric resistors for heater systems, for FCL units with GLL grilles.

SIT3; SIT5 Interface Cards

Interface cards for connecting fan coils to control panels.

Accessory Details: Temperature Probes

VMF-SW1 Water Temperature Probe (Cold Water)

Probe for VMF System thermostats for cold water circuit in 4-pipe systems.

SW3 Minimum Water Temperature Sensor

Probe for PXAE control panel to detect heating coil water temperature.

SW4 Water Temperature Probe (2-pipe;Hot Water)

Probe for VMF System thermostats for 2-pipe and 4-pipe hot water circuits.

SWA Water and Air Temperature Probe

Probe for FMT20AW panels to detect ambient air or water temperature.

VMF System Control Panels

VMF-E4; VMF-E4 D Wall-Mounted Control Panel

Wall-mounted thermostat control panel for VMF range thermostats.

TTL Network Example (FCLs Only)

Diagram showing a TTL network with only FCL units.

VMF-E5 B;E5 N Network Example (FCLs Only)

Diagram showing a network with VMF supervisor and FCL units.

TTL Network Example (Mixed Fan Coils)

Diagram showing a TTL network with mixed fan coil types.

VMF-E5 B;E5 N Network Example (Mixed Fan Coils)

Diagram showing a VMF network with supervisor and mixed fan coils.

VMF System Supervision

VMF-E5 B;E5 N Supervision Interface

Main supervision interface for VMF-E5B/E5N systems.

Recessed Supervisor Control Panel

Description of VMF-E5B/E5N panels, features, and system management capabilities.

Control Panel Accessories

FMT10 Control Panel

Thermostat for fan coils with simplified controls and 3 speeds.

FMT20 AW Control Panel

Thermostat with LCD display, probe options, and built-in installation.

WMT10 Control Panel

Electromechanical thermostat for 4-pipe, 2-pipe systems with heater.

PX Control Panel

Control panel with selector for manual speed control.

Control Panel Accessories (Continued)

PXAE Control Panel

Multifunction electronic thermostat for fan coils, with simplified controls.

PX2; PX2 C6 Control Panels

Control panels for manual speed control and fan speed selection.

Installation Precautions

System Installation Examples

Wiring diagrams illustrating system configurations.

Maximum Installation Height

Guideline to not install the unit at heights above three metres.

Fresh Air and Adjacent Room Connection

Connecting the unit to fresh air ducts and airflow to adjacent rooms.

Installation of Module 600 Unit

Installation Location Planning

Considerations for choosing the installation location for the machine.

Mounting Rods

Procedure for installing M8 threaded rods for frame support.

Unit Handling with Brackets

Instruction to use brackets for handling, not hydraulic connections.

Electric Box and Grid Accessories

Information on the electric box and its supplied grid accessories.

Safety Cable Attachment

Instruction to fix the safety cable to the electric box and grid frame.

Air Probe Installation (GLL10 M;10 R)

Instructions for installing air probes on GLL10M/10R grilles.

Screw Tightening Torque Warning

Warning on screw tightening torque to avoid damaging the tray.

Unit Levelling

Adjusting unit position using support brackets for level installation.

Functioning Test

Procedure for starting the fan coil and performing a test.

Module 600 Installation Steps

Installation Near a Wall

Guidance for closing flow inlet with gasket when installed near a wall.

Installation of Module 840 Unit

Module 840 Installation Location

Considerations for choosing the installation location for Module 840.

Module 840 Mounting Rods

Procedure for installing M8 threaded rods for Module 840 frame support.

Module 840 Unit Handling

Instruction to use brackets for handling Module 840 units.

Module 840 Electric Box and Grille Accessories

Info on electric box and GLL20/GLL20R grille accessories.

Air Probe Installation (GLL20 R)

Instructions for installing air probes on GLL20R grilles.

Module 840 Screw Torque Warning

Warning on screw tightening torque to avoid damaging the tray.

Module 840 Safety Cable Attachment

Instruction to attach safety cable snap hook to grid frame and fan grid.

Module 840 Unit Levelling

Adjusting Module 840 unit position for level installation.

Module 840 Functioning Test

Procedure for starting Module 840 and performing a test.

Disassembly for Maintenance

Electric Box Maintenance

Procedure for accessing and maintaining the electric box.

Installation Near Wall (Module 600;840)

Connections

Hydraulic Connections

Details on flat stroke fittings, gaskets, and mandatory valve accessory for 4-pipe systems.

Condensate Drain Connections

Instructions for connecting the condensate drain pipe and managing the basin.

External Fresh Air Intake Connections

Connecting the unit to a fresh air intake duct via flange.

Airflow to Adjoining Room Connection

Connecting the unit for conditioned air flow to an adjacent room via flange.

Electric Connections

GLL10; GLL20 Electric Connections

Details on direct connection to outlet or circuit, power supply, and cable requirements.

GLL10 M;10 R;20 R;10 N;20 N Electric Connections

Electric connection details for GLL units with receiver/thermostat.

Filter Installation and Replacement (Module 600)

Filter Installation and Replacement (Module 840)

Dimensional Data [mm] (Module 600 Series)

Dimensional Data [mm] (Module 840 Series)

Wiring Diagrams Legend

FCL GLL10;GLL20 Wiring Diagram

FCL VL GLL10;GLL20 Wiring Diagram

FCL GLL10 M Wiring Diagram

FCL GLL10 R; GLL20 R Wiring Diagram

FCL GLL10;GLL20 Wiring Diagrams with Control Panels

FCL GLL10;GLL20 with WMT10 Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with WMT10 control panel.

FCL GLL10;GLL20 with PXAE Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with PXAE control panel.

FCL GLL10;GLL20 Wiring Diagrams with Control Panels (Continued)

FCL GLL10;GLL20 with FMT10 Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with FMT10 control panel.

FCL GLL10;GLL20 with FMT20 AW Wiring Diagram

Wiring diagram for FCL GLL10/GLL20 with FMT20AW control panel.

FCL GLL10 N; GLL20 N Wiring Diagram

FCL VL GLL10 N; GLL20 N Wiring Diagram

System Wiring Examples

FCL System Wiring with PXAE, SIT3, SIT5

Wiring example for FCL units with PXAE and SIT interface cards.

AERMEC FCL 64 Specifications