Double Set point
By enabling the double set point function (Enable double set point) by means of a contact that is
not live, connected to the digital input ID3, it is possible to decide whether to use the normal set
points or double set alternatively (e.g. night-time functioning).
ID3 closed = use 2nd set point
ID3 open = use normal set points
Priority set point
If several functions co-exist, the Multichiller will use the highest priority set point. The set points are
listed below starting from the one with highest priority.
Double set
External compensation
External set
Set point (from dispaly)