22
AVMFE18LJ1101 - 6795746_02
E18 TECHNICAL CHARACTERISTICS
Power supply 230V AC +/-10%, 50-60 Hz
Max input power (excluding loads controlled by TRIACs) 4.5VA
Digital inputs 4 free contacts
Analogue inputs 3 for reading NTC 10K probes
Analogue outlets 2 (0-10V) for Inverter reference and valve control
Digital outputs 2, 230V AC with Triac
Assembly On the machine
Protection rating IP20 (referring to the containment plastic)
Storage conditions -20T80°C, humidity 80% non-condensing
Operating conditions 0T50°C, humidity 80% non-condensing
Software class Class A
SPECIAL CONNECTIONS FOR E18
Power supply Screw terminals, 5mm pitch
Cable section - min=0.5mm
2
max=2.0mm
2
Accessory command outputs (Valves, Plasmacluster,
germicidal lamp, etc.)
Screw terminals, 5mm pitch
Cable section - min=0.5mm
2
max=1.3mm
2
Maximum cable length = 30m
EC digital input Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
2
max=1.0mm
2
Maximum cable length = 100m
MS digital input Sliding contact
Maximum cable length = 3m
SP digital input Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
2
max=1.0mm
2
Maximum cable length = 100m
Analogue inputs (SA-SW) Quick plug-in connections
Maximum cable length = 3m
Analogue input (SC) Quick plug-in connection
Maximum cable length = 30m
TTL local serial Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
2
max=1.0mm
2
Maximum cable length = 30m
RS485 supervision serial Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
2
max=1.0mm
2
Maximum cable length = 1000m
Output power supply 12V DC Screw terminals, 3.81mm pitch
Cable section - min=0.2mm
2
max=1.0mm
2
Maximum cable length = 30m
Reference 0-10V for Inverter 2-pole screw terminal, 3.81mm pitch
Outputs 01-10V 2-pole screw terminal, 3.81mm pitch
Inverter fault input 2-pole screw terminal, 3.81mm pitch
COMPLIANCE WITH EC MARK
The following directives are used for reference:
• Low Voltage Directive 2006/95/EC
• Electromagnetic Compatibility Directive 2004/108/EC.