Main Menu Group Constant LCD Display Range Unit
Factory
Setting
Remark Page
Programming D
Auxiliary Relay 1
D-01 Set Aux Relay 1 Mode
OFF, ON,
Solar Voltage,
Output Volts,
Battery Volts,
OUT Current,
BATT Current,
Temperature
Battery Temp.
Time
Battery SOC,
Output Volts
─
OFF 5-10
D-02
Aux RY1 ON Condition See Below
See
Below
See
Below
5-10
When D-01= Solar Voltage 0~150/0~250 0.1V 0 5-10
When D-01=Output Volts 0~64 0.1V 0 5-10
When D-01=Battery Volts 0~64 0.1V 0 5-10
When D-01=OUT Current 0~80 1A 0 5-10
When D-01=BATT Current -500~500 1A 0 5-10
When D-01= Temperature -20~100 1
℃
0 5-10
When D-01=Battery Temp. -20~100 1℃ 0 5-10
When D-01= Time
00~23 Hr
00~59 Min
1 Min 0 5-10
When D-01=Battery SOC 0~100 1% 0 5-10
D-03
AuxRY1 OFF Condition See Below
See
Below
See
Below
5-11
When D-01= Solar Voltage 0~150/0~250 0.1V 0 5-11
When D-01=Output Volts 0~64 0.1V 0 5-11
When D-01=Battery Volts 0~64 0.1V 0 5-11
When D-01=OUT Current 0~80 1A 0 5-11
When D-01=BATT Current -500~500 1A 0 5-11
When D-01= Temperature -20~100 1
℃
0 5-11
When D-01=Battery Temp. -20~100 1
℃
0 5-11