B-07: Set Absorption Time
Use Constant B-07 to adjust the length of Absorption time. The factory setting is 2 hours
(displayed as 02:00).
B-08: Set Float Voltage
Use Constant B-08 to adjust the Float voltages. The default set values are based on the battery
type and capacity selected. It is not advisable to change default settings unless advised by the
battery manufacturer or supplier.
Battery Type Float Volts Range
Factory
Setting
FLOODED 12.9V~14.2V 13.8V
AGM 12.8V~14.2V 13.2V
GEL 12.8V~14.1V 13.5V
※ The above values are based on 12V systems. The values x 2 are for 24V systems; the values x 3 are
for 36V systems and the values x 4 are for 48V systems.
B-09: Set Equalize Voltage
This constant is only displayed if Flooded is selected as battery type (B-02). Use Constant B-09 to
select the Equalize voltages. The default values are based on the battery voltage and capacity
selected. It is not recommended to change default settings unless advised so by the battery
manufacturer or supplier.
Battery Type
Battery
Voltage
Equalization Volts Range
Factory
Setting
FLOODED
12V 14.7V~16.4V 15.6V
24V 29.4V~32.8 V 31.2V
36V 44.1V~49.2V 46.8V
48V 58.8V~65.6V 62.4V
B-10: Set MAX EQU. Time
This constant is only displayed if Flooded is selected as battery type (B-02). Use Constant B-10 to
select the time of equalization time. The factory setting is 2 hours (displayed as 02:00).
B-11: Set Days Between EQU
This constant is only displayed if Flooded is selected as battery type (B-02). Use Constant B-11 to
select the number of days between equalization charges. The factory setting is OFF.
B-12: Manual Equalize
This constant is only displayed if Flooded is selected as battery type (B-02). Use Constant B-12 to