choose between manual and automatic equalization settings.
Press ENTER key to select Yes for manual equalization and then it will display the Equalize
voltage set in B-09 and the Max. EQU time set in B-10. Press ENTER key again to start the
manual equalization.
※ During equalization, only ESC key is active to leave the equalization process screen.
After the manual equalization starts, BAT displays Battery voltage. Battery temperature and Equalizing
will alternately blink. CHARGE displays charging current. Finally, the remaining time for equalization
charge is counted down.
WARNING: Before the manual equalization is selected, AIMS MPPT+ should be connected to Battery
Temperature Sensor (BTS-3). If it is not connected to BTS-3, “Warning, Bat. Sr Not Connected” is
displayed.
Press ESC key to select No to return to the display of Group B.
Group C
MPPT Setup
C-01: Set MPPT Type
Use Constant C-01 to set up the MPPT type: P and O, Scan and Hold, Percentage, Hold Input V.
The factory setting is P and O.