Technical Manual : Part No 6259485 V1.15.0_08_2018
Technical Data - Ecodesign
URAC75D, URAC100D, URAC125D, URAC150D, URAC175D
Notes:
URAC75D
URAC100D
URAC125D
URAC150D
URAC175D
SEPR
1,3,5
4.1
4.74
5.08
4.76
4.66
SEPR Tier
Not Compliant
Tier 1 (2018)
Tier 2 (2021)
Tier 1 (2018)
Tier 1 (2018)
Annual Electricity Consumption
kWh/a
n/a
175771
206626
268502
325690
Rated Refrigerant Capacity P
A
1,3,5
kW
n/a
111.9
141.0
171.6
203.9
Rated Power Input D
A
kW
n/a
36.3
43.0
55.6
66.3
Rated EER
DC,A
n/a
3.08
3.28
3.09
3.07
Declared Refrigerant Capacity P
B
1,3,5
kW
n/a
122/92.1
153.6/123.5
186.9/141
222.2/176
Declared Power Input D
B
kW
n/a
29.8/23
35.3/28.2
45.8/35.2
55.0/44.2
Declared EER
DC,B
n/a
4.09/4.01
4.35/4.38
4.08/4.01
4.04/3.98
Declared Refrigerant Capacity P
C
1,3,5
kW
n/a
128.1/96.3
129.3/97.6
196.3/147.6
184.8/136.1
Declared Power Input D
C
kW
n/a
25.9/20
24.6/19.6
39.5/30.5
38.5/30.8
Declared EER
DC,C
n/a
4.95/4.82
5.25/4.98
4.96/4.84
4.79/4.41
Declared Refrigerant Capacity P
D
1,3,5
kW
n/a
96.3/64.9
129.3/97.6
147.6/99.4
184.8/136.1
Declared Power Input D
D
kW
n/a
18.9/13.9
23.8/18.7
28.9/21.2
36.6/28.8
Declared EER
DC,D
n/a
5.10/4.66
5.44/5.21
5.11/4.68
5.05/4.72
SSCEE
2,3,5
%
117.0
143.2
161.4
144.4
142.7
SSCEE Tier
Not Compliant
Not Compliant
Tier 2 (2021)
Not Compliant
Not Compliant
Rated Cooling Capacity P
rated,c
2,4,5
n/a
n/a
141.6
n/a
n/a
Declared Cooling Capacity 35°C Pdc
2,3,5
kW
n/a
n/a
141.0
n/a
n/a
Declared EER
d
35°C
n/a
n/a
3.28
n/a
n/a
Declared Cooling Capacity 30°C Pdc
2,3,5
kW
n/a
n/a
125.5/95.6
n/a
n/a
Declared EER
d
30°C
n/a
n/a
4.12/4.02
n/a
n/a
Declared Cooling Capacity 25°C Pdc
2,3,5
kW
n/a
n/a
104.0/53.1
n/a
n/a
Declared EER
d
25°C
n/a
n/a
4.86/4.15
n/a
n/a
Declared Cooling Capacity 20°C Pdc
2,3,5
kW
n/a
n/a
57.5/0
n/a
n/a
Declared EER
d
20°C
n/a
n/a
5.11/0
n/a
n/a
Sound Power Level L
WA
dB(A)
n/a
n/a
85.0
n/a
n/a
Off mode P
OFF
kW
n/a
n/a
0.137
n/a
n/a
Thermostat-off mode P
TO
kW
n/a
n/a
0.607
n/a
n/a
Standby Mode P
SB
kW
n/a
n/a
0.145
n/a
n/a
Crankcase heater mode P
CK
kW
n/a
n/a
0.104
n/a
n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.