ULTIMA REMOTE AIR COOLED
Chillers
45
Technical Manual : Part No 6259485 V1.15.0_08_2018
Technical Data - Ecodesign
URAC300DQ, URAC330DQ, URAC360DQ, URAC400DQ, URAC450DQ
Notes:
URAC300DQ
URAC330DQ
URAC360DQ
URAC400DQ
URAC450DQ
SEPR
1,3,5
5.13
4.94
4.82
4.95
4.76
SEPR Tier
Tier 2 (2021)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Tier 1 (2018)
Annual Electricity Consumption
kWh/a
474455
553382
632532
684110
779534
Rated Refrigerant Capacity P
A
1,3,5
kW
327.7
367.7
410.3
455.2
498.9
Rated Power Input D
A
kW
108.2
123.7
139.0
154.1
176.8
Rated EER
DC,A
3.03
2.97
2.95
2.95
2.82
Declared Refrigerant Capacity P
B
1,3,5
kW
358.2/299.9
346.7/274
454.6/380.8
428.3/340.1
549.1/459.9
Declared Power Input D
B
kW
88.2/73.3
86.9/70.6
115.6/96.7
108.3/87.9
145.6/122
Declared EER
DC,B
4.06/4.09
3.99/3.88
3.93/3.94
3.95/3.87
3.77/3.77
Declared Refrigerant Capacity P
C
1,3,5
kW
320.7/257.4
375.2/293.6
413/331.3
464.5/366
497/398.7
Declared Power Input D
C
kW
60.9/50.9
73.6/60.2
82.9/69.6
90.8/74.8
101.3/85.4
Declared EER
DC,C
5.27/5.06
5.10/4.88
4.98/4.76
5.12/4.89
4.91/4.67
Declared Refrigerant Capacity P
D
1,3,5
kW
262.2/198.3
299.8/236.1
339/256.4
374.3/291.3
407.7/308.3
Declared Power Input D
D
kW
46.3/37.2
55.1/46
63.9/51.5
68.4/56
77.0/62.4
Declared EER
DC,D
5.66/5.33
5.44/5.14
5.30/4.97
5.47/5.20
5.30/4.94
SSCEE
2,3,5
%
148.2
143.3
138.5
143.4
132.7
SSCEE Tier
Not
Compliant
Not
Compliant
Not
Compliant
Not
Compliant
Not
Compliant
Rated Cooling Capacity P
rated,c
2,4,5
n/a
n/a
n/a
n/a
n/a
Declared Cooling Capacity 35°C
Pdc
2,3,5
kW
n/a
n/a
n/a
n/a
n/a
Declared EER
d
35°C
n/a
n/a
n/a
n/a
n/a
Declared Cooling Capacity 30°C
Pdc
2,3,5
kW
n/a
n/a
n/a
n/a
n/a
Declared EER
d
30°C
n/a
n/a
n/a
n/a
n/a
Declared Cooling Capacity 25°C
Pdc
2,3,5
kW
n/a
n/a
n/a
n/a
n/a
Declared EER
d
25°C
n/a
n/a
n/a
n/a
n/a
Declared Cooling Capacity 20°C
Pdc
2,3,5
kW
n/a
n/a
n/a
n/a
n/a
Declared EER
d
20°C
n/a
n/a
n/a
n/a
n/a
Sound Power Level L
WA
dB(A)
n/a
n/a
n/a
n/a
n/a
Off mode P
OFF
kW
n/a
n/a
n/a
n/a
n/a
Thermostat-off mode P
TO
kW
n/a
n/a
n/a
n/a
n/a
Standby Mode P
SB
kW
n/a
n/a
n/a
n/a
n/a
Crankcase heater mode P
CK
kW
n/a
n/a
n/a
n/a
n/a
(1) Nominal conditions as stated in EU 2016/2281 Table 22.
(2) Nominal conditions as stated in EU 2016/2281 Table 21.
(3) Performance data (Nett) is supplied in accordance with EN14511-1:2013.
(4) Performance data (Gross) is supplied excluding absorbed pump power as per EN14511-1:2013.
(5) All performance data based upon standard waterside configuration.
(6) Please contact Airedale regarding Non Compliant selections.