System Parameters and Default Values
72
This section provides a listing of all changeable parameters in the PGD user interface. Authorized technicians
may use the information in this section to change factory settings. The main menu and associated menu
screens are covered in
Main Screen on Page 53.
5.1 Step Test Menu Parameters
The Step Test menu is used to access the step test. See Table 3-10 on Page 61 for additional information
and instructions for executing the step test.
5.2 HVAC Config Menu Parameters
The HVAC Config menu contains configuration options for the following components, each of which has its
own menu:
Supply (Evaporator) Fan
Condenser Fan
EEV
Compressor
Inverter
Alarms
Table 5-1 Parameters in the Supply Fan Menu
Menu Screen
Option
Description
Default
Supply Fan
Min Speed
Minimum allowed fan speed
30%
Max Speed
Maximum allowed fan speed
100%
Prime Power Fail
Maximum fan speed when the unit has no AC
Power
80%
Supply Fan PID
Kp
Proportional control setting
4.0
Ki
Integral control setting
30
Kd
Derivative control setting
0
DX Fan Speed
Fixed DX Max Speed
Supply fan speed when the compressor is on
and system is in fixed speed mode
100%
Variable DX Max
Speed
Supply fan speed when the compressor is on
and system is in normal speed (variable)
mode
93%
Dehumidification
Speed
Supply fan speed during dehumidification
75%
Variable DX Min
Speed:
Minimum fan speed during mechanical
cooling
70%