EasyManua.ls Logo

AIRSYS UNICOOL 28V1B5 - Page 93

Default Icon
121 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
System Update
93
Model numbers of connected units.
5. (Optional) Record any other settings, such as temperature setpoint, that are to be maintained.
Step 3: Upgrade Controller (ASMUC)
1. Connect the computer to the micro USB port on the controller board inside the ASMUC. The controller
should become visible as external storage “USB Drive” on the PC.
2. Copy the AP1 file to the “Upgrade” folder.
3. Copy the HTTP folder to the root directory and overwrite the existing files.
4. Disconnect the USB cable from the controller. The upgrade process will automatically start.
5. Once the upgrade is complete, the screen will display “Upload successful” and return to the main screen.
This may take up to 5 minutes.
6. Power cycle the controller by turning off the breaker and turning back on after a few seconds.
Step 4: Reload Saved Parameters on Controller
1. Pressure Up and Down together.
2. In the “Master/HVAC select” screen, select “Master Controller” and press Enter.
3. Press Esc.
4. Press Prg and enter the default password (0004). Press Enter.
5. Press Up or Down to reach “Control Config” and press Enter.
6. Press Enter at “Network”
7. Re-enter the saved information (a-d)

Other manuals for AIRSYS UNICOOL 28V1B5