SR SR
HST
n
< HSTOH1 Norm
(*) Normal (Norm) – No protection status is ON.
Stop-Rise (SR) – System is in protection.
HzDown1 (D1) - System is in protection.
HzDown2 (D2) - System is in protection.
12.7.7 System Over Power Protection
Power
n
-Power
n-1
Power
n
<-50 [-50,-1] 0 [1,50] >50
Power
n
> OVRPWR5 SC SC SC SC SC
OVRPWR4 ≤ Power
n
<
OVRPWR5
D1 D1 D2 D2 D2
OVRPWR3 ≤ Power
n
<
OVRPWR4
SR SR D1 D2 D2
OVRPWR2 ≤ Power
n
<
OVRPWR3
SR SR SR D1 D1
OVRPWR1 ≤ Power
n
<
OVRPWR2
Norm Norm Norm
SR SR
Power
n
< OVRPWR1 Norm
12.7.8 Outdoor Coil Deicing Protection
In the deicing protection, IFAN is forced OFF.
12.7.8.1 Deicing Starting Conditions
Deicing operation will start when either one of the following conditions exist:
• Case 1: OCT<–DST AND
TLD > DI
• Case 2: OCT<-4 AND
TLD>100 minutes
• Case 3: OCT is Invalid AND TLD > DI
• Case 4: Unit is just switched to STBY AND OCT<-DST
• Case 5: compressor is stopped during heating operation, OCT<-DST AND TLD>DI,
OCT – Outdoor Coil Temperature
OAT – Outdoor Air Temperature
TLD – Time from Last Deicing
DI – Deicing Interval (Time Interval Between Two Deicing)
DT- Deicing Time