SP2/SP4/SP8/SP8-X20 Manual
Updated until firmware 476 - 34 -
But all of the readings depend on the environment like the number of sensors you have online
and your email and SNMP trap alert settings.
Question:
Is there a way to reboot the sensorProbe unit’s web interface remotely?
Answer:
Yes, you can reboot the unit’s web interface remotely using this SNMP command and OID here:
snmpset -m all -v 1 -c <community> <IPaddress> .1.3.6.1.4.1.3854.1.2.2.1.106.0 i 1
Question:
Is there any way to edit the content of the email alerts that are sent out from my sensorProbe
unit?
Answer:
Yes, we have have added a separate e-mail notification function. You can set this by using the
following SNMP command:
snmpset -m all -v 1 -c <community> <ip address> .1.3.6.1.4.1.3854.1.2.2.1.112.0 I <separate>
When <community> is admin password <ip address> is ip address of the unit
<separate> is for the separate e-mails or not if this value is 1 it will have the separate e-mails
if this value is 0 it will not have the separate e-mails.
Question:
I have forgotten the IP address that my sensorProbe is configured with. Is there a way I can
determine this IP?
Answer:
Yes, you can unplug the power cord, then plug it back in, to cycle the power on the sensorProbe
while you have the IPSet utility software running on your PC. When you open the IPSet utility, it
will say “Recycle power to sensorProbe” as shown in this screen shot below):