PR200_3-EN-125853-1.4
© All rights reserved. Subject to technical changes and misprints.
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
PR200
Programmable relay
WARNING
Installation may only be performed when the relay and all
connected devices are powered off.
Voltage on the terminals can be dangerous!
CAUTION
It is necessary to observe the polarity while connecting 24V DC
power supply! Voltage reversal can damage the device.
CAUTION
Installation and maintenance may only be carried out by
specialist personnel using the correct tools!
NOTICE
It is recommended to configure and program the device prior to
installation and wiring.
1. Ordering information
Supply voltage
230 230 (94…264) V AC
24 24 (19…30) V DC
I/O
1 8 DI, 6 DO
2 8 DI, 4 AI, 8 DO, 2 AO (4-20 mA)
4 8 DI, 4 AI, 8 DO, 2 AO (0-10 V)
Interfaces
0 none
1 RS485
2 2 × RS485
2. Specifications
Table 1 General specification
Parameter
Value
230.1.X 230.2/4.X 24.1.X 24.2/4.X
Power supply
230 (94…264) V AC;
50 (47…63) Hz
24 (19…30) V DC
Power consumption 10 VA 17 VA 10 W 10 W
Galvanic isolation 2830 V 1780 V
Integrated voltage
source
24±3 V DC,
100 mA
Galvanic isolation
1780 V
IP Code IP20
Dimensions 123 × 108 × 58 mm
Mounting DIN rail (35 mm)
Weight approx. 600 g
Table 2 Digital inputs
Parameter
Value
230.X.X 24.X.X
Input voltage
230 V AC 24 V DC
Input voltage, max.
264 V AC 30 V DC
HIGH level
159…264 V /
0.75…1.5 mA
8.5…30 V / 2…15 mA
LOW level 0…40 V / 0…0.5 mA -3…+5 V / 0…15 mA
Pulse length, min.
50 ms 2 ms
Response time, max.
100 ms 30 ms
Galvanic isolation against
other circuits
2830 V
Table 3 Analog inputs
Parameter Value
ADC resolution 12 bit
Analog mode
Input signal
0-10 V, 4-20 mA, 0-4
Input resistance (for 0-10 V)
61
Shunt resistance
(for 4-20 mA)
121 Ω
Basic error ±0.5 %
Temperature influence
±0.5 % / 10 °C
Digital mode
HIGH/LOW threshold
(adjustable in ALP)
1…8 V
LOW/HIGH threshold
(adjustable in ALP)
2…9 V
Pulse length, min.
5 ms
Signal frequency, max.
100 Hz
Table 4 Digital outputs
Parameter Value
Type relay (NO)
Switching capacity
AC
5 A, 250 V AC (resistive load)
DC
3 A, 30 V DC
Parameter Value
Load current at 5 V DC, min.
10 mA
Service life,
electrical
AC
200,000 switching cycles
DC
100,000 switching cycles
Galvanic isolation against
other circuits
2830 V, in groups of 2
Galvanic isolation between
output groups
1780 V
Table 5 Analog outputs
Parameter Value
Output signal 4-20 mA (X.2.X), 0-10 V (X.4.X)
External voltage supply
15…30 V
Basic error, max.
±0.5%
Temperature influence
±0.05% / 10°C
Inductive load, max
(for 4-20 mA)
50 μH
Signal conversion time
100 ms
DAC resolution 10 bit
Galvanic isolation against
other circuit
2830 V
3. Operating conditions
The device is designed for natural convection cooling.
The following environmental conditions must be observed:
clean, dry and controlled environment, low dust level
closed non-hazardous areas, free of corrosive or flammable gases
Table 6 Operating conditions
Condition
Permissible range
Ambient temperature
-20…+55 °C
Transportation and storage
Relative humidity up to 80 % (at +25 °C, non-condencing)
Attitude
up to 2000 m above sea level
IP code IP20
EMC immunity
conforms to IEC 61000-6-2
EMC emission conforms to IEC 61000-6-4
4. Installation
Fig. 1 Dimensions
Fig. 2 Installation
Installation:
1. Place the device on a DIN rail as shown in Fig. 2.
2. Press the device firmly against the DIN rail in the direction of arrow 2
until the latch locks.
3. Wire the device using the supplied terminal blocks.
Removing:
1. Take off the terminal blocks without disconnecting wires.
2. Insert a screwdriver into the eyelet of the slide interlock.
3. Loosen the slide interlock and then remove the relay from the DIN rail.
PR200 is equipped with plug-in terminal blocks which enable quick
replacement of the device without disconnecting the existing wiring.

Other manuals for Akytec PR200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Akytec PR200 and is the answer not in the manual?

Akytec PR200 Specifications

General IconGeneral
BrandAkytec
ModelPR200
CategoryRelays
LanguageEnglish