154 Rockwell Automation Publication 1756-UM540E-EN-P - December 2017
Chapter 8 Calibrate the ControlLogix Analog I/O Modules
12. Click Next.
The Group High Reference Results dialog box indicates the status of each 
channel after calibrating for a high reference. 
13. If channels are OK, click Next.
If any channel reports an error, return to step 11
 and click Retry until the 
status is OK.
If the error persists indefinitely, click Stop to exit calibration. The channel 
remains calibrated to the accuracy level achieved at factory calibration.
14. When the Calibration Completed dialog box appears, click Finish.