What to do if output is ON in code but not on module in Allen-Bradley I/O Systems?
- BBrett MartinezAug 7, 2025
If the output is ON in your user application code but not ON at the output module, you should: * Verify that at least one of the connections to the output module is active. * Verify that the output is ON in the output module tags. * Confirm whether all of the connections in the chassis are faulted, including the Ethernet modules. If so, troubleshoot the Ethernet communication issue. * Troubleshoot the error code displayed in Module Properties > Connection tab.