12 Firmware Update Instructions for Ethernet, Enhanced and ControlNet PLC-5 Programmable Controllers
4. Since you removed the controller from the chassis, you must reenter the
computer’s Ethernet IP address and subnet mask (for example,
255.255.255.0 for Class C).The controller should have an IP address
with the same first three octets as the computer’s Ethernet network
interface address.
If it doesn’t, then you can assign the IP either by going online with the
controller over DH+ or serially, and configuring the IP address for
Channel 2 via the channel configuration screen (uncheck the BOOTP
enabled box). Or, by setting up a BOOTP server with this module’s
assigned IP address.
5. In ControlFLASH:
6. When the update is successful:
– restore all connections to the controller
– download the program back into memory and make certain that it
runs properly
Your firmware update is complete. If you have any questions, call Rockwell
Automation Technical Support at 440.646.3223.
Click OK.
The update process is now complete.
If an error occurs, click
View Log to see specific error
information.
The Status windows displays the result of the update.
If an error occurs, it is displayed in this window.
At the “Cycle Power” prompt, click OK