12 Rockwell Automation Publication 193-IN080A-EN-P - September 2018
E300 Electronic Overload Relay
Setting the Hardware Switches
Figure 8 - E300 Relay DeviceNet Node Addressing
For example, when the left dial is set to 0 and the right dial is set to 1, the resulting DeviceNet node address is: 01.
For node address switch values in the range of 0 to 63, cycle power to the E300 relay to initialize the new setting.
Using RSNetWorx for DeviceNet
Follow these additional steps for node address switch settings in the range of 64…76 and 78…98. To begin the configuration of an E300 relay using
software, execute the RSNetWorx software and complete the following procedure. You must use RSNetWorx for DeviceNet Revision 27.00.00 or
later.
Recognizing the E300 Relay Online
1. Launch the RSNetWorx software, then select Online from the Network pull-down menu.
2. Select the appropriate DeviceNet personal computer interface, then click OK.
3. If the RSNetWorx software gives notification to upload or download devices before viewing configuration, click OK to upload or download
these devices.
Node Address Function Node Address Function
00…63 Set node address to xx 88 Reset to factory defaults
64…76
78…98
Software sets node address 77 Administration mode
TIP
You must configure the E300 DeviceNet drivers using RSLinx™ software before they become available to RSNetWorx™ software
x10 x1
Network Information
-Serial Number
-Firmware Revision
Node Address