EasyManuals Logo

Allen-Bradley PanelView Plus 1000 Technical Data

Allen-Bradley PanelView Plus 1000
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #13 background imageLoading...
Page #13 background image
Rockwell Automation Publication 2711P-TD001D-EN-P - February 2011
Wiring and Grounding Guidelines for PanelView Plus Terminals 13
Earth/Ground Connection for Isolated DC Terminals
PanelView Plus 700 to 1500 terminals with an isolated DC power supply have an
earth/ground terminal that you must connect to a low-impedance earth/ground.
The earth/ground connection is on the rear of the display module. The
earth/ground terminal wiring requires a minimum wire gauge.
The earth/ground terminal is typically connected to a system grounding bus. If
the grounding bus has tapped holes, the conductor from the functional earth
terminal must have a ground lug on the ground bus end. A bolt should pass
through a star washer, then through the ground conductor lug, then into the
ground bus.
Use the shortest, practical wire length to connect the earth/ground to a
low-impedance earth/ground. The ground wire must be either green or green
with a yellow stripe. Refer to local wiring codes and regulations for grounding
requirements.
Figure 5 - Earth/Ground Connection for 700 to 1500 Isolated DC Terminals
IMPORTANT
The earth/ground connection to ground is mandatory. This connection is
required for noise immunity, reliability, and Electromagnetic Compliance
(EMC) with the European Union (EU) EMC directive for CE-mark
conformance and for safety by Underwriters Laboratory.
Table 6 - Earth/Ground Wiring for Isolated DC Terminals
PE Symbol Wire Type Wire Gauge Terminal Screw Torque
GND Cu 90 °C (194 °F)
Copper
Stranded or solid
2.1…5.3 mm
2
(14…10 AWG)
1.13…1.36 N•m
(10…12 lb•in)
ATTENTION: Damage or malfunction can occur when a voltage potential
exists between two separate ground points. Make sure the PanelView
Plus terminal does not serve as a conductive path between two ground
points at different potentials.
Enclosure Wall
To Grounding Electrode System
Tapped Hole
Ground Lug
Bolt
Star Washer
Ground Bus
Ground Bus
Earth/Ground to Ground Bus

Other manuals for Allen-Bradley PanelView Plus 1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley PanelView Plus 1000 and is the answer not in the manual?

Allen-Bradley PanelView Plus 1000 Specifications

General IconGeneral
Display Size10.4 inches
Resolution640 x 480 pixels
TouchscreenAnalog resistive
Operating SystemWindows CE
Memory64 MB RAM
Storage64 MB Flash
Communication PortsEthernet, RS-232, USB
Input Voltage24V DC
Display TypeColor TFT
ProcessorXScale
EnclosureNEMA 4X
Operating Temperature0°C to 50°C

Related product manuals