44 Rockwell Automation Publication 750-IN001O-EN-P - October 2014
Chapter 3 Lift and Mount the Drive
Install Floor Mount Drive
with Cabinet Options Bay
and Wiring Bay
Frame 9 drives configured with both the cabinet options bay and wiring bay ship
in two sections. The following procedure describes how to join the wiring bay to
the cabinet options bay.
1. Remove external wrapping, bus bar cover, and locate joining hardware.
Joining hardware is shipped with the wiring bay.
Position the Drive Cabinets and Cabinet Options Bay
2. Release the factory-assembled drive cabinets and cabinet options bay from
the shipping skid.
Description Quantity Description Quantity
M8 x 16 mm Cabinet Joining Screw 20 M10 Nut with Washer 12
M10 x 45 mm Carriage Bolt 12 M6 x 40 mm bolts 4
Bus Bar Clamp Plate 12 M6 Flange Nuts 4
M8 x 16
13 mm
Drive Cabinets
Cabinet Options Bay
IP54, NEMA 12 Enclosure Rating Shown