508033-02 Issue 2135 Page 7 of 48
Electronic Ignition
At the beginning of the heat cycle the integrated control
monitors the rst stage and second stage combustion air
inducer prove switch. The control will not begin the heating
cycle if the rst stage prove switch is closed (by-passed).
Likewise the integrated control will not begin the second
stage heating cycle if the second stage prove switch is
closed, and will remain in rst stage heat. However, if the
second stage prove switch closes during the rst stage
heat pre-purge, the control will allow second stage heat.
Once the rst stage prove switch is determined to be open,
the combustion air inducer is energized on low (rst stage)
heat speed. When the di󰀨erential in the prove switch is
great enough, the prove switch closes and a 15-second
pre-purge begins.
NOTE: During abnormal conditions such as low supply
voltage or low outdoor temperatures and the low re
pressure switch does not close, the combustion air inducer
will switch to high re. After a 15 second pre-purge the
high re pressure switch will close and the unit will begin
operation on high re. After 10 to 20 seconds of high re
operation the unit will switch to low re.
After the 15-second pre-purge period, the SureLight
®
ignitor
warms up for 20 seconds after which the gas valve opens
for a 4-second trial for ignition. The ignitor energizes during
the trial until ame is sensed. If ignition is not proved during
the 4-second period, the control will try four more times
with an inter purge and warm-up time between trials of 35
seconds. After a total of ve trials for ignition (including
the initial trial), the control goes into Watchguard-Flame
Failure mode. After a 60-minute reset period, the control
will begin the ignition sequence again.
Two Stage Operation / Thermostat Selection DIP
Switch
The control can be utilized in two modes: SINGLE-STAGE
thermostat or TWO-STAGE thermostat. The thermostat
selection is made using a DIP switch and must be positioned
for the particular application. DIP switch 1, labeled T”STAT
HEAT STAGE is factory-set in the OFF position for use
with a two-stage thermostat. Move the DIP switch to ON
for use with a single stage thermostat.
While in the single-stage thermostat mode, the burners will
always re on rst-stage heat. The combustion air inducer
will operate on low speed and indoor blower will operate on
low heat speed. The unit will switch to second stage heat
after a “recognition period”. DIP switch 2, labeled SECOND
STAGE DELAY, is factory set in the OFF position for a 7
minute recognition period. The switch can be moved to the
ON position for a 12 minute recognition period, after which
time the unit will switch to secondstage heat.
While in the two-stage thermostat mode (two DIP switch
setting) the burners will re on rst-stage heat. The
combustion air inducer will operate on low speed and
indoor blower will operate on low heat speed. The unit
will switch to second-stage heat on call from the indoor
thermostat. If there is a simultaneous call for rst and
second stage heat, the unit will re an rst stage heat and
switch to second stage heat after 30 seconds of operation.
See Sequence of Operation ow charts in the back of this
manual for more detail.
PIN# Function
1 Ignitor
2
Combustion Air Inducer High
Speed
3
Combustion Air Inducer Low
Speed
4 Combustuion Air Inducer Neutral
5 Ignitor Neutral
Table 1. SureLight
®
Control 5 Pin Terminal
Designation
PIN# Function
1 Gas Valve High Fire
2 Second Stage Prove Switch
3 Rollout In
4 Ground
5 24V Hot
6 Primary Limit In
7 Gas Valve Low Stage
8 Gas Valve Common
9 24V Neutral
10 Ground
11 Rollout Switch Out
12 1st Stage Prove Switch
Table 2. SureLight
®
Control 12 Pin Terminal
Designation
PIN# Function
1 Data Input From Motor
2 Common
3 Not Used
4 Data Output To Motor
5 5 Volt Bias Supply
6
Not Used
Table 3. SureLight
®
Control 6 Pin Terminal
Designation