EasyManua.ls Logo

Allmand 185 CFM - Troubleshooting Engine Start and Operation; Engine Start Failure Causes; Low Temperature Operation Guide

Allmand 185 CFM
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Not for
Reproduction
18 ALLMAND.COM
Engine Fails to Start
1. If the engine fails to start after performing starting
procedure, steps 1 - 4, do not keep the starter
running.
2. Set the starter switch to STOP, wait
approximately 2 minutes, then repeat the startup
procedure.
3. If the repeated startup procedure does not allow
the engine to run, check for the following causes:
No fuel
Clogged fuel filter
Discharge of battery or low cranking speed
Ambient temperature is too low
Starting the Compressor at Low Temperature
NOTICE When operating compressor under cold
weather conditions below
23°F (-5°C):
Use SAE10W-30 (CJ-4) for the engine oil.
When the unit is used in a cold region and
possible freezing is expected, it is recommended
to use LLC (Antifreeze) for the coolant.
Adjust mixing ratio of LLC (Antifreeze) with water
according to the temperature.
Use LLC (Antifreeze) within the range of its
mixing ratio between 35 and 60%.
If LLC (Antifreeze) in the water exceeds more
than 60%, it may decrease its antifreezing effect.
(Upon delivery from the works, LLC density is
55%).
Use LLC (anti-freeze) which conforms to one
of such standards: SAE JB13, SAE J1034 and
ASTEM D3306.
Battery should always be fully charged.
Follow the designated regulations to dispose of
LLC (Antifreeze).
When it is difficult to start engine in cold weather,
complete the following steps:
1. Fully close the service valves.
2. Start engine by following steps 1 - 6 in Starting
the Compressor.
CAUTION When operating the unit in
a low temperature, change engine oil, compressor
oil, LLC , and diesel fuel according to the ambient
temperature.
Gauge Indication While Operating Compressor
NOTICE Minimum discharge air pressure is 58 psi (4
bar) during operation. Continuing equipment operation
at a lower pressure than the above pressure may
cause overheating, since it affects the separation of
lubricating oil inside the oil separator and reduces
the oil flow to the compressor air-end, resulting in
temperature rise.
Make sure to check that gauges or each
component of the compressor are properly
working, or if there is any air-leak, oil-leak, water-
leak or fuel-leak etc.
During normal operation, each indication of
instruments is shown in the table below. Refer to
the table for daily checks.
Discharge
Pressure Gauge
In Operation
Full Load
* 58 to 100 psi
(4 to 6.9 bar)
No Load
(Unload)
* 116 to 131 psi
( 8 to 9 bar)
At purge
control
(AUTO IDLE)
* 36 to 58 psi
( 2.5 to 4bar)
* Values may vary slightly depending on the operating conditions and
other factors.