19
Subject to change without notice | 83056600cUK – Translation into English of the original German operating manual | ait-deutschland GmbH
Advantages of low-salt operation:
Low corrosion-promoting properties
No formation of mineral scale
Ideal for closed heating circuits
ideal pH value due to self-alkalinisation after lling
the system
If necessary, simple alkalinisation to pH value 8.2
by adding chemicals
7.3 Fill,ushandventheatsource
Water and the following antifreeze products are
approvedforllingthebrinecircuit:
Monopropylene glycol
Monoethylene glycol
Ethanol
Methanol
For operation of the heat source with water or
water-antifreeze mixture, ensure that the water
fulls the quality specications of the heating
water side.
Checkthatfrostprotectionto–13°Cisensured.
Ensure that the antifreeze is compatible with the
pipe, seal and other component materials used on
site.
Drain pipe of the safety valve is connected.
Room is ventilated.
1. Flush heat source system.
2. Mix antifreeze with water thoroughly with the
required ratio, before adding to the heat source.
3. Check the concentration of the water-antifreeze
mixture. Frost protection: –13 °C
4. Fill the heat source with the water-antifreeze
mixture.
5. Flush until the system is air-free.
7.4 Vent the circulation pump
of the heat source
NOTE
The diagram shows the unit variant with
cooling. In the unit variant without cooling the
circulation pump is located in the same place.
1. Place vessel for collecting discharging liquid
under the outlet.
2. Undo screw-on cap in the middle of the circulation
pump.
3. Wait until liquid is discharged uniformly.
4. Screwthecapbackontightly.
5. Unscrew the front panel of the module box.
6. Dispose of collected liquid according to the local
regulations.
7. Set system pressure to 1 bar.