Maintenance
Maintena
nce
plan
G51
-
-0
01EN07
14/18
02--2011
© ALSTOM 2010. All rights reserved. Informat
ion contained in
this document is indicative only. No
representati
on or
warrant
y is
given or should
be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liabili
ty and
is subject to
change without notice. Reproduction, use or disclosure to
third parties, without express writt
en authority, is
strictly prohibited.
GRID
Detail of ci
rcuit
-
-
breaker maintenance operations
, continued
CAU
TION
:
INSP
ECT
ION
CANCOMME
NCEONL
Y
AFT
ER
THECAP
ACI-
TOR HAS BEEN DISCHARGED AND EARTHED IN A DURABLE WAY.
IF
THESE SAFETY INSTRUCT
IONS ARE
IGNORED
,
THE PERSONNEL
MAY BE ENDANGERED.
Capacitors
(if
applica
ble)
Check condition of capacitors as follows :
D
clean capacitor insulating surfaces using a dry cloth,
D
check tighteni
ng torque of capacitor mountin
gs on the
flange of the enclo-
sure, if need be, change sealing washers,
D
make sure that there are no traces of oil or moisture on the capacitors,
D
check the braid connec
tion between the
capaci
tor and t
he circuit-brea
ker
casing.
Current transformers
(if applicable)
Check condition of transformers as follows :
D
clean transformer insulating surfaces using a dry cloth,
D
check electrical connections on CT terminal blocks and cubicle,
D
check attachment of CT to the enclosure, tightening to supporting stud
torque.
D
ins
pec
t,
whe
re
app
lica
ble
,
the
CT
s
bra
id
con
nec
tion
to
the
main
con
duc
tor
,
for CT with an electrostatic shield.
Potential
transformers
(where applicable)
Check condition of potential transformers as follows :
D
clean potential transformer insulating surfaces using a dry cloth,
D
check electrical connections on PT terminal blocks and cubicle,
D
check attachment of potential transformer, tightening torque,
D
inspect, the attachments of the braid connection of potential transformer.
Lightning arrester
(where applicable)
Check condition of lighting arrester as follows :
D
clean lightning arrester insulating surfaces using a dry cloth,
D
check attachments of lightning arrester to the pole, tightening torque.
Tightness of
enclosure
(if applicable)
If the enclosure is under pressure, check the tightness of cover seals by ap-
plying a soap solution around the entire periphery of the cover.
Also check
tightness of
all the
enclos
ure viewports.
Replac
ement of
en-
closur
e
cover seals
(if applicable)
Re
fer
af
fec
ted
se
cti
on
R
EP
LA
CE
MEN
T
OF
EN
CL
OSU
RE
COV
ER
SEALS”.