End of equipment service life
Disma
ntling and
recov
ery of
compon
ents
from a circuit breaker
G80
-
-0
00EN02
4/6
02--2011
© ALSTOM 2010. All rights reserved. Informat
ion contained in
this document is indicative only. No
representati
on or
warrant
y is
given or should
be
relied on that it is complete or correct or will apply to any particular project. This will depend on the technical and commercial circumstances. It is
provided without liabili
ty and
is subject to
change without notice. Reproduction, use or disclosure to
third parties, without express writt
en authority, is
strictly prohibited.
GRID
III
-
-
Categories and treatment of
the materials
1
-
-
Treatment of
SF6 gas
The SF6 gas will be recycled in accordance with the recommendations of
the IEC 60480 Standard.
However, when recovering the SF6 gas, it is important to respect the
following precautions:
-
-
Weigh the reci
pients used befor
e and after filling, so as to
ensure
traceability of the weights recovered
-
-
For each recipie
nt, carry out a
measur
ement of the purity of
the SF6
gas and a search for the decomposition products (SO2, HF)
In case of absence of a local waste processing channel for the recycling of
SF6, we recommend a return to our site in Villeurbanne, where we
propos
e
reproc
essing via
our European service providers.
2 -
-
Materials to be
recycled
Metals form the main constituent of a gas insulated substation.
The main types of metal making up a substation are:
-
-
Steel: steelwork structure
, f
asteners
, electrical cubicle frames, etc.
-
-
Alumini
um: moulded or
mechan
ical welded enclosur
es, conductor bars,
electrod
es,
etc.
-
-
Bolted fasteners
, threaded rods, rating and name plates
-
-
Bare copp
er: electrical contac
ts, etc.
-
-
Insulated cop
per: electrica
l cable
It is important to separate these different metals when dismantling the
substation at the end of its service life. In particular for small sub---
assemblies made up of various materials.
In certain simple cases, it is sufficient to remove the fasteners ensuring the
assembly and, in other cases, specific instructions shall be given.
The aluminium and
copper element
s
must, under no
circum
stance
s,
be mixed.
Specific waste processin
g
channels associa
ted with
these
mater
ials do
not allow
for perfect separatio
n
during their processing.
In cases where it is impossible to separate them, the component
must be sent for incineration.