Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 103/108
4.7.1.1 Submenu Fault Record for P126 & P127
The Fault Record submenu makes it possible to read up to five stored fault records,
that occurred when programmed thresholds where exceeded.
The fault records are generated by the operation of trip relay RL1.
NOTE: All measurement magnitude values refer to the transformer
primary side.
RECORD
Heading of RECORD menu.
Fault Record
Heading of Fault Record submenu
To gain access to the submenu points, press 2.
Record Number
5
Selection of the Fault Record number 5 to be displayed
(selection: 1, 2, 3, 4 or 5). To modify this fault record
number, press 0 then using 8 the required number is
entered. Press 5 to confirm choice.
Fault Time
13:05:23
Displays the time when the fault was recorded. The
format of the time is hh:mm:ss.
In this example the fault was recorded at 1:05:23 pm.
Fault Date
12/11/01
Displays the date when the fault was recorded. The
format of the Date is DD/MM/YY.
In this example, the fault was recorded on November
12th 2001.
Active Set Group
1
Displays the active setting group (1 or 2).
Faulted Phase
PHASE A
Displays the phase, where a fault occurred, for the
chosen fault record. (NONE, PHASE A, B, C, EARTH)
Threshold
-----
Displays the origin of the fault that generated the trip
order.
Common for P126 & P127 are:
tIe>, tIe>>, tIe>>>, tPe/IeCos>, tPe/IeCos>>, Trip
tUe>>>>, tI>, tI>>, tI>>>, tI<, tI2>, tI2>>,
tI2>>>, Thermal q, Brkn. Cond, Aux 1, Aux 2, EQU
A, EQU B, EQU C, EQU D
Only valid for P127:
tU>, tU>>, tU<, tU<<
Magnitude
1200 A
Displays the magnitude value of the fault: Voltage,
current, earth power. The value is based on the
amplitude at 50 or 60 Hz.