Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 19/108
4.2.4 Example: Setting LED 5 for P126:
CONFIGURATION
Heading of CONFIGURATION menu.
To gain access to the LED submenu, press 2 and 6
until the submenu is reached.
Led
Heading Led submenu.
To gain access to Led 5 submenu, press 2. To set the
led assignment press 5 and 8 2 to scroll available
selections. Press 5 to confirm choice.
Led 5
Ie> No
Setting choice Yes: LED 5 lights up when Ie> threshold
is exceeded.
Setting choice No: No operation when Ie> threshold is
exceeded.
Led 5
tIe> No
Setting choice Yes: LED 5 lights up when tIe> delay
time has elapsed.
Setting choice No: No operation when tIe> delay time
has elapsed.
Led 5
Ie>> No
Setting choice Yes: LED 5 lights up when Ie>>
threshold is exceeded.
Setting choice No: No operation when Ie>> threshold
is exceeded.
Led 5
tIe>> No
Setting choice Yes: LED 5 lights up when tIe>> delay
time has elapsed.
Setting choice No: No operation when tIe>> delay
time has elapsed.
Led 5
Ie>>> No
Setting choice Yes: LED 5 lights up when Ie>>>
threshold is exceeded.
Setting choice No: No operation when Ie>>>
threshold is exceeded.
Led 5
tIe>>> No
Setting choice Yes: LED 5 lights up when tIe>>> delay
time has elapsed.
Setting choice No: No operation when tIe>>> delay
time has elapsed.
Led 5
Pe/IeCos> No
Setting choice Yes: LED 5 lights up when Pe> or
IeCos> threshold is exceeded.
Setting choice No: No operation when Pe> or IeCos>
threshold is exceeded.
Led 5
tPe/IeCos> No
Setting choice Yes: LED 5 lights up when tPe> or
IeCos> delay time has elapsed.
Setting choice No: No operation when tPe> or IeCos>
delay time has elapsed.
Led 5
Pe/IeCos>> No
Setting choice Yes: LED 5 lights up when Pe>> or
IeCos>> threshold is exceeded.
Setting choice No: No operation when Pe>> or
IeCos>> threshold is exceeded.

Table of Contents