Technical Guide P12y/EN FT/D22
User Guide
MiCOM P125/P126/P127 Page 55/108
4.5.3.7 Threshold Menu I>>
I>> ?
Yes
Selection of the second alarm threshold function for
phase OC (I>>).
Setting choice: No, Yes
If the user selects Yes, the following window is shown:
If the user selects No, the next window will show the
threshold menu I>>>.
I>>
10.00 In
Displays setting value of the alarm threshold.
The threshold setting range is from 0.5 to 40 In, in
steps of 0.01 In.
t I>>
150.00 s
Displays setting value of the trip threshold.
The setting range is from 0 to 150 s, in steps of 10ms.
By pushing 2 the next window will display the I>>>?
4.5.3.8 Threshold Menu I>>>
I>>> ?
Yes
Selection of the third alarm threshold function for
phase OC (I>>>). Setting choice: No, Yes, DIR.
If the user selects Yes, the following window is shown:
If the user selects DIR, the directional choice window is
shown.
If the user selects No, the next window will show the
submenu [50/51] Phase OC.
I>>>
10.00 In
Displays setting value of the alarm threshold (I>>>).
The threshold setting range is from 0.5 to 40 In, in
steps of 0.01 In.
t I>>>
150.00 s
Displays setting value of the trip threshold.
The setting range is from 0 to 150 s, in steps of 10ms.
By pushing 2 the next window will display the [50/51] PHASE OC