P12y/EN FT/D22 Technical Guide
User Guide
Page 64/108 MiCOM P125/P126/P127
q Trip
100%
Displays the percentage applicable to the thermal
overload trip threshold.
The q Trip setting range is from 50 to 200%, in steps of
0.01.
q Alarm ?
Yes
Selection of the thermal overload alarm function.
Setting choice: No, Yes
If the user selects Yes, the following window is shown:
If the user selects No, no new window will be shown.
q Alarm
80%
Displays the percentage applicable to the thermal
overload alarm threshold.
The q Alarm setting range is from 50 to 200%, in steps
of 0.01.
By pushing 2 the next window will display the [49] Therm OL