P12y/EN FT/D22 Technical Guide
User Guide
Page 70/108 MiCOM P125/P126/P127
Dead Time
tD4 180.00 s
Displays setting value of the forth cycle dead time (tD4)
for the autoreclose function.
The setting range is from 0.01 to 600 s, in steps of
10ms.
Reclaim Time
tR 180.00 s
Displays setting value of the reclaim time (tR) for the
autoreclose function.
The setting range is from 0.01 to 600 s, in steps of
10ms.
Inhib Time
tI 180.00 s
Displays setting value of the inhibit time (tI) for the
autoreclose function (following a manual CB closure).
Setting range from 0.01 s to 600 s, in steps of 10 ms.
4.5.11.5 Selection Menu [79] Phase and Earth Re-closing Cycle Enable
Phase Cycles
4
Displays setting of autoreclose cycles externally started
by a phase protection trip signal.
Setting choice is from 0 to 4 cycles.
E/Gnd Cycles
4
Displays setting of autoreclose cycles externally started
by an earth protection trip signal.
Setting choice is from 0 to 4 cycles.
By pushing 2 the next window will display the [79] Autoreclose