P12y/EN FT/D22 Technical Guide
User Guide
Page 80/108 MiCOM P125/P126/P127
4.6.5.1 Submenu Outputs Relays for P125
AUTOMAT. CTRL
Heading of AUTOMAT. CTRL menu.
To gain access to the Output Relays submenu, press 2
and 6 until the submenu is reached.
Output Relays
Heading of Output Relays submenu.
To navigate within submenu points, press 8 2. To
modify setting, press 5. Use 8 2 4 6 to scroll and set
available selections. Press 5 to confirm choice.
Trip :65432
00010
Assigning output signal Trip (RL1) to other output
relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie> :65432
00010
Assigning first alarm threshold for earth fault
overcurrent (Ie>) to other output relays; i.e. to output 3
(RL3). Setting choice: 1 assigns the output relay; 0 no
assignment.
tIe> :65432
00010
Assigning first trip threshold for earth fault overcurrent
(tIe>) to other output relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie_R> :65432
00010
Assigning first trip threshold for directional earth fault
overcurrent from the inverse trip zone (Ie_R>) to the
output relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie>> :65432
00010
Assigning second alrm threshold for earth fault
overcurrent (Ie>>) to the output relays; i.e. to output 3
(RL3). Setting choice: 1 assigns the output relay; 0 no
assignment.
tIe>> :65432
00010
Assigning second trip threshold for earth fault
overcurrent (tIe>>) to the output relays; i.e. to output 3
(RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie_R>> :65432
00010
Assigning second trip threshold for directional earth
fault overcurrent from the inverse trip zone (Ie_R>>) to
the output relays; i.e. to output 3 (RL3).
Setting choice: 1 assigns the output relay; 0 no
assignment.
Ie>>> :65432
00010
Assigning third alarm threshold for earth fault
overcurrent (Ie>>>) to the output relays; i.e. to output
3 (RL3). Setting choice: 1 assigns the output relay; 0 no
assignment.