7 Protection Parametre Settings
P50 Agile P15D
7-4
P15D/EN TM/B
2 PROTECTION PARAMETRE SETTINGS
2.1 System Data
Observation Default setting Setting Range
Language English Not Editable
Frequency 50Hz 50Hz /60Hz step 10 Hz
This setting determines the system frequency.
Com Port USB USB /RP
This setting selects the front port (USB) or rear port (RS485) for communication.
Password 0000 0000-9999
USB Address 1 Not editable
This cell sets the fixed USB port address for the relay.
USB Parity None Not editable
This cell controls the parity format used in the data frames. It is important that both relay and configuration tool are set with the same
parity setting.
USB Baud rate 57600 Not editable
This cell controls the communication speed between relay and configuration tool. It is important that both relay and configuration tool are
set to the same speed setting.
Active Group Group 1 Group 1/Group 2
This setting displays the active setting group as selected in CONFIGURATION menu.
2.2 CB Control settings
Sr. No Parametre Default Setting Setting Range
1 Password 0000 0000 to 9999
This setting is used to enter a new password.
2 Trip Test Disabled Enabled/Disabled
This setting enables or disables Trip Test function. When the function is enabled and the Trip Test key is pressed the relay immediately
provides trip command. This trip command is also extended to breaker coil, so the entire trip operation from relay to circuit breaker can be
checked.
3 Latch Relay Disabled Enabled/Disabled
This setting activates or deactivates the Latch Relay function.
4 Trip Block Disabled Enabled/Disabled
This setting enables or disables the Trip Block function. By enabling this function the user can block the trip command.
2.3 Date and Time settings
Sr. No Parameter Default setting Setting Range
1. Password 0000 0000 to 9999
This setting is used to enter a new password.
2. Local Time
Enable
Fixed Fixed / Flexible / Disabled