2.2.11 Protocol Mapping
Sr. No. INF Description GI TYP COT FUN
1 Semantics of INFORMATION NUMBER : System Functions in monitor direction
0 End of general interrogation - 8 10 255
0 Time synchronization - 6 8 255
2 Reset FCB - 5 3 160
3 Reset CU - 5 4 160
4 Start/Restart - 5 5 160
5 Power on - 5 6 160
Note: X under GI heading means DI Status is included in General Interrogation response.
Sr. No. INF Description GI TYP COT FUN
2 Semantics of INFORMATION NUMBER : Status Indications in monitor direction
21 Test X 1 9,11 127
18 Protection active X 1 1,7,9,11,12,20,21 160
19 LED Reset X 1 1,7,11,12,20,21 160
22 Local parameter setting X 1 9,11 160
27 Status 1 X 1 1,7,9,11 160
28 Status 2 X 1 1,7,9,11 160
29 Status 3 X 1 1,7,9,11 160
30 Status 4 X 1 1,7,9,11 160